| Plan Review Notes For Permit 22040982 |
| Permit Number |
22040982 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-01 14:43:29 | OFFICE BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING A0.02 SHOWS NEW CORRIDOR WALL AS 1 HOUR FIRE | | | RATED - DRAWING A1.11 SHOWS NEW CORRIDOR WALL AS | | | DESIGNATION "S2" - DRAWING A5.11 SHOWS WALL DESIGNATION | | | "S2" AS NON-FIRE RATED. PLEASE CLARIFY. | | | | | | 2) DOOR 001 SHOULD BE FIRE RATED FOR A 1 HR FIRE RATED | | | WALL PER FBC 716.5 - - DOOR GLAZING NEEDS TO COMPLY | | | WITH FBC 716.2 |
|