| 2023-05-09 12:05:04 | INSUFFICIENT | | | | | | 1) REPEAT COMMENT: THE SURVEY SHOWS THE POWER POLE THAT | | | WILL SUPPLY THE UNDERGROUND POWER ON PRIVATE PROPERTY | | | AND REQUIRING A CROSSING OF THE PRIVATE PROPERTY TO | | | REACH THE HANDHOLE AT STA 0+00. IN ORDER FOR THE | | | UNDERGROUND ELECTRIC TO CROSS PRIVATE PROPERTY, IT MUST | | | BE LOCATED WITHIN A GENERAL UTILITY EASEMENT. THE | | | SURVEY DOES NOT SHOW AN EASEMENT AT THIS LOCATION. IF | | | THERE IS AN EASEMENT, IT MUST BE SHOWN ON THE SURVEY | | | AND THE UNDERGROUND ELECTRIC MUST CLEARLY BE SHOWN IN | | | THE EASEMENT. IF NO EASEMENT IS PRESENT, THE | | | UNDERGROUND ELECTRIC MUST COME FROM AN ALTERNATIVE | | | LOCATION. | | | | | | 2) REPEAT COMMENT: SHEET E201 DOES NOT SHOW A POLE THAT | | | MEETS THE CITY'S STEALTH REQUIREMENTS. THE ORIGINAL | | | SUBMITTAL SHOWED A COMPLIANT POLE DESIGN. SHEETS A201 | | | AND A502 SHOW A COMPLIANT POLE. ALL PLANS MUST SHOW | | | CITY COMPLIANT POLES. | | | | | | 3) THE POLE HEIGHT AND STYLE (SUBJECT TO THE CORRECTION | | | OF SHEET E201) MEET CITY REQUIREMENTS. THE POLE COLOR | | | AT THIS LOCATION IS CORRECTLY SHOWN AS RAL/RAYCAP 7042 | | | TRAFFIC GREY A. | | | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | | [email protected] | | | |
|