| 2022-12-19 16:00:27 | INSUFFICIENT |
| | |
| | 1) THE SURVEY SHOWS THE POWER POLE THAT WILL SUPPLY THE |
| | UNDERGROUND POWER ON PRIVATE PROPERTY AND REQUIRING A |
| | CROSSING OF THE PRIVATE PROPERTY TO REACH THE HANDHOLE |
| | AT STA 0+00. IN ORDER FOR THE UNDERGROUND ELECTRIC TO |
| | CROSS PRIVATE PROPERTY, IT MUST BE LOCATED WITHIN A |
| | GENERAL UTILITY EASEMENT. THE SURVEY DOES NOT SHOW AN |
| | EASEMENT AT THIS LOCATION. IF THERE IS AN EASEMENT, IT |
| | MUST BE SHOWN ON THE SURVEY AND THE UNDERGROUND |
| | ELECTRIC MUST CLEARLY BE SHOWN IN THE EASEMENT. IF NO |
| | EASEMENT IS PRESENT, THE UNDERGROUND ELECTRIC MUST COME |
| | FROM AN ALTERNATIVE LOCATION. |
| | |
| | 2) THE UPDATED SURVEY SHOWS THE FULL LENGTH OF THE |
| | POWER ROUTE, TO INCLUDE THE HANDHOLES AND BORE PITS, IS |
| | LOCATED WITHIN THE RIGHT-OF-WAY, HOWEVER, THE LOCATION |
| | OF THE GAS LINE AT STA 0+00 IS NOT SHOWN AT THE SAME |
| | LOCATION ON THE SURVEY AND SHEET E101. BASED ON THE |
| | SURVEY, THERE IS A DIRECT CONFLICT WITH THE HANDHOLE |
| | AND ITS EXCAVATION AND THE GAS LINE. YOU NEED TO |
| | PROVIDE VERIFICATION FROM FPU THAT THEY DO NOT OBJECT |
| | TO THE PROPOSED INSTALLATION LOCATION OF YOUR |
| | FACILITES. |
| | |
| | 3) THE LAT/LON FOR THE POLE ON THE SURVEY AND SITE PLAN |
| | IS SHOWN AS THE HANDHOLE LOCATION ON THE POWER ROUTE |
| | PLAN. PLEASE ENSURE THAT ALL PLANS ARE LABELED |
| | CORRECTLY. |
| | |
| | 4) THE NEWLY UPLOADED SHEET E201 DOES NOT SHOW A POLE |
| | THAT MEETS THE CITY'S STEALTH REQUIREMENTS. THE |
| | ORIGINAL SUBMITTAL SHOWED A COMPLIANT POLE DESIGN. |
| | SHEETS A201 AND A502 SHOW A COMPLIANT POLE. |
| | |
| | 5) THE POLE HEIGHT AND STYLE (SUBJECT TO THE CORRECTION |
| | OF SHEET E201) MEET CITY REQUIREMENTS. THE POLE COLOR |
| | AT THIS LOCATION IS CORRECTLY SHOWN AS RAL/RAYCAP 7042 |
| | TRAFFIC GREY A. |
| | |