2022-06-29 10:57:46WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22040936
 ADD: 701 S OLIVE AVE # 1903
 CONT: STONESTYLES
 TEL: 561-809-5115
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JUNE 29TH/2022
 ACTION: DENIED
  
 1)2ND REQUEST. THE 3 SUBMITTED FLOOR PLANS DRAWN BY
 LYNN AUSTIN WILL HAVE TO HAVE EITHER A ARCHITECT OR
 ENGINEER CREATE THEIR OWN PLANS. PROJECTS GREATER THAN
 $25,000.00 ARE REQUIRED TO BE SIGNED AND SEALED.
 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1) (C)
 ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER
 BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE
 SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE
 REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45.
  
 2) 2ND REQUEST. IT APPEARS THE PROPOSED FLOOR PLAN AND
 FLOOR PLAN 001 DO NOT MATCH UP, DISCREPANCY IN PLANS.
 SHEET 001 FLOOR PLAN THE MAIN DOUBLE DOOR ENTRY. THE
 CORRIDOR OUTSIDE THE UNIT TURNS 90 DEGREES BUT THE
 FRONT ENTRY DOORS ARE AT A 45 DEGREE ANGLE TO THE
 CORRIDOR, SHEET 003 THE PROPOSED FLOOR PLAN HAS THE
 FRONT ENTRY DOOR PARALLEL TO THE CORRIDOR DISCREPANCY
 IN PLANS. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 SHOW AS A FULL FLOOR PLAN WITH CORRIDOR.
  
 3)2ND REQUEST. AS VIEWED FROM PROPOSED FLOOR PLAN THE
 KITCHEN AND BATHROOMS HAVE BEEN REVERED THAT WILL
 CREATE NEW PLUMBING PENETRATIONS OF THE POST TENSIONED
 FLOOR SYSTEM. POST TENSION SLAB/ NEW HOLES. THE PLAN IS
 SILENT AS IF THE LOCATION OF THE EXISTING TUB DRAIN IS
 GOING TO BE REUSED IN THE SAME LOCATION. IF NOT, THEN
 THE FLOOR SLAB WILL NEED TO BE X-RAYED TO FIND THE POST
 TENSION CHORD LOCATIONS. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) 2ND REQUEST. -PENETRATIONS FIRESTOP SYSTEMS
 (HORIZONTAL ASSEMBLIES). IF A NEW FLOOR PENETRATION IS
 MADE FOR THE FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW
 COMPLIANCE WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  