| 2022-05-09 17:12:34 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22040936 |
| | ADD: 701 S OLIVE AVE # 1903 |
| | CONT: STONESTYLES |
| | TEL: 561-809-5115 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY MAY 09TH/2022 |
| | ACTION: DENIED |
| | |
| | 1) THE 3 SUBMITTED FLOOR PLANS DRAWN BY LYNN AUSTIN |
| | WILL HAVE TO HAVE EITHER A ARCHITECT OR ENGINEER CREATE |
| | THEIR OWN PLANS. PROJECTS GREATER THAN $25,000.00 ARE |
| | REQUIRED TO BE SINGED AND SEALED. 481.229 EXCEPTIONS; |
| | EXEMPTIONS FROM LICENSURE (1) (C) ANY OTHER TYPE OF |
| | BUILDING COSTING LESS THAN $25,000.00, EXCEPT A SCHOOL, |
| | AUDITORIUM, OR OTHER BUILDING INTENDED FOR PUBLIC USE, |
| | PROVIDED THAT THE SERVICES OF A REGISTERED ARCHITECT |
| | SHALL NOT BE REQUIRED FOR MINOR SCHOOL PROJECTS |
| | PURSUANT TO 1013.45. |
| | |
| | 2) IT APPEARS THE PROPOSED FLOOR PLAN AND FLOOR PLAN |
| | 001 DO NOT MATCH UP, DISCREPANCY IN PLANS. SHEET 001 |
| | FLOOR PLAN THE MAIN DOUBLE DOOR ENTRY. THE CORRIDOR |
| | OUTSIDE THE UNIT TURNS 90 DEGREES BUT THE FRONT ENTRY |
| | DOORS ARE AT A 45 DEGREE ANGLE TO THE CORRIDOR, SHEET |
| | 003 THE PROPOSED FLOOR PLAN HAS THE FRONT ENTRY DOOR |
| | PARALLEL TO THE CORRIDOR DISCREPANCY IN PLANS. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) AS VIEWED FROM PROPOSED FLOOR PLAN THE KITCHEN AND |
| | BATHROOMS HAVE BEEN REVERED THAT WILL CREATE NEW |
| | PLUMBING PENETRATIONS OF THE POST TENSIONED FLOOR |
| | SYSTEM. POST TENSION SLAB/ NEW HOLES. THE PLAN IS |
| | SILENT AS IF THE LOCATION OF THE EXISTING TUB DRAIN IS |
| | GOING TO BE REUSED IN THE SAME LOCATION. IF NOT, THEN |
| | THE FLOOR SLAB WILL NEED TO BE X-RAYED TO FIND THE POST |
| | TENSION CHORD LOCATIONS. 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 4) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE |
| | FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE |
| | WITH THE 2020 FBC-B SECTION 714.5.1.2. |
| | THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY |
| | A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN |
| | ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL |
| | HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT |
| | NOT LESS THAN THE REQUIRED RATING OF THE FLOOR |
| | PENETRATED. |
| | |
| | 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |