Plan Review Notes
Plan Review Notes For Permit 22040912
Permit Number 22040912
Review Stop P
Sequence Number 1
Notes
Date Text
2022-04-28 07:35:451ST REVIEW FBC-2020 PLUMBING
 PERMIT-22040912
 4/28/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TWO BACKFLOW PREVENTERS ARE BEING INSTALLED AT THE
 SAME BUILDING ADDRESS. ARE THERE TWO SEPARATE WATER
 SERVICES TO THE BUILDING OR IS ONE BACKFLOW FOR THE
 FIRE LINE? PLEASE CLARIFY AND NOTE THAT BACKFLOW
 PREVENTER INSTALLATION FOR FIRE LINE REQUIRES A FIRE
 PROTECTION CONTRACTOR II OR V LICENSE- FL. STATUTE
 633.334.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  