| Plan Review Notes For Permit 22040905 |
| Permit Number |
22040905 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-22 12:18:47 | FIRE REVIEW COMMENTS: | | | PROVIDE THE TYPE OF NEW FLOORING TO BE INSTALLED TO | | | INCLUDE SPECIFICATIONS ON FIRE PERFORMANCE AND | | | CLASSIFICATION OF THE MATERIAL. NFPA 101 10.2 | | | ANY AND ALL WORK ON A LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) REQUIRES A SEPARATE PERMIT | | | AND DRAWINGS TO BE SUBMITTED AND APPROVED AND THE WORK | | | SHALL BE PERFORMED BY QUALIFIED CONTRACTORS. | | | FIRE REVIEWER: | | | C.R. WALKER | | | 561-804-4762 | | | [email protected] | | | |
|