Plan Review Notes
Plan Review Notes For Permit 22040888
Permit Number 22040888
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-04 17:35:031ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22040888
 5/4/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE POTABLE WATER SERVICE LINE DETAILS FOR THE
 OFFICE TRAILER- SECS. 301.4 & 602.1 FBC P. PLEASE
 INCLUDE A SITE PLAN SHOWING THE LOCATIONS OF SERVICE
 LINE, POINT OF CONNECTION TO THE MAIN SERVICE LINE,
 WATER METER AND BACKFLOW PREVENTER. INDICATE THE TYPE
 AND SIZE OF WATER LINE AND BURIAL DEPTH- SEC. 605.3
 FBC.
  
 2) IN ACCORDANCE WITH SEC. E WPB UTILITIES CROSS
 CONNECTION MANUAL AN RPZ BACKFLOW PREVENTER FOR THE
 POTABLE WATER SERVICE LINE IS REQUIRED. THE
 INSTALLATION SHALL BE UNDER SEPARATE PERMIT- SEC. 105.1
 & 107.2.1 WPB.
  
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTERS IN ACCORDANCE WITH SECTION 105.1 WPB AND
 SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  