| 2022-05-04 17:35:03 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22040888 |
| | 5/4/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE POTABLE WATER SERVICE LINE DETAILS FOR THE |
| | OFFICE TRAILER- SECS. 301.4 & 602.1 FBC P. PLEASE |
| | INCLUDE A SITE PLAN SHOWING THE LOCATIONS OF SERVICE |
| | LINE, POINT OF CONNECTION TO THE MAIN SERVICE LINE, |
| | WATER METER AND BACKFLOW PREVENTER. INDICATE THE TYPE |
| | AND SIZE OF WATER LINE AND BURIAL DEPTH- SEC. 605.3 |
| | FBC. |
| | |
| | 2) IN ACCORDANCE WITH SEC. E WPB UTILITIES CROSS |
| | CONNECTION MANUAL AN RPZ BACKFLOW PREVENTER FOR THE |
| | POTABLE WATER SERVICE LINE IS REQUIRED. THE |
| | INSTALLATION SHALL BE UNDER SEPARATE PERMIT- SEC. 105.1 |
| | & 107.2.1 WPB. |
| | |
| | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTERS IN ACCORDANCE WITH SECTION 105.1 WPB AND |
| | SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |