Plan Review Notes
Plan Review Notes For Permit 22040875
Permit Number 22040875
Review Stop M
Sequence Number 1
Notes
Date Text
2022-05-05 07:40:521ST REVIEW FMC
 PERMIT: 22040875
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1 AND FMC 312.1
  
 2) SHEET M-2: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR THE NO. OF PEOPLE BASED OF TABLE
 403.3.1.1. THE CALCULATIONS APPEAR TO BE LOW FOR THE
 MUSEUM/GALLERIES AND THE CONFERENCE ROOM. FMC 403.3.1.1
  
 3) BECAUSE THIS DESIGN USED DX UNITS AND THE OAU UNIT
 PLEASE PROVIDE THE OUTDOOR AIR REQUIREMENTS FOR EACH
 ROOM NOT JUST A GENERAL GALLERY/MUSEUM FOR THE ENTIRE
 AREA. PLEASE SHOW HOW ADJOINING ROOMS WILL BE PROVIDED
 WITH THE REQUIRED OUTDOOR AIR I.E. THE FOYER AND EAST
 GALLERY DO NOT SHOW OUTDOOR AIR DUCTS. THE FOYER DOES
 SHOW DOORS THAT CAN SEPARATE IT FROM THE REST OF THE
 BUILDING. FMC 403.3.1.1
  
 4) SHEET M-10: PLEASE UPDATE THE CODE REFERENCES AS WE
 ARE CURRENTLY ENFORCING THE 2020 FMC. ALL REFERENCES
 SHOULD CALL FOR THE CURRENT EDITIONS REFERENCED IN THE
 2020 FMC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  