Plan Review Notes
Plan Review Notes For Permit 22040875
Permit Number 22040875
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-04-28 12:32:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF EXIT SIGNS ALONG THE
 EXIT PATHS NOR EXITS.
  
 PER NFPA 101, CH 13 EXISTING ASSEMBY OCCUPANCIES AND CH
 7 MEANS OF EGRESS, THEY ARE REQUIRED:
  
 13.2.10 MARKING OF MEANS OF EGRESS.
 13.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS
 IN ACCORDANCE
 WITH SECTION 7.10
  
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN ACCOR DANCE WITH SECTION 7.10 WHERE REQUIRED
 IN CHAPTERS 11 THROUGH 4
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS
  
 PLEASE REVIEW AND CORRECT/PROVIDE.
  
  
 2) THERE ARE NO INDICATIONS OF EMERGENCY LIGHTING.
  
 13.2.9 EMERGENCY LIGHTING.
 13.2.9.1 EMERGENCY LIGHTING, OTHER THAN THAT PERMITTED
 BY 13.2.9.3,
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 7.9.
 13.2.9.2 PRIVATE PARTY TENTS NOT EXCEEDING 1200 FT2
 (112 M2
 ) SHALL NOT
 BE REQUIRED TO HAVE EMERGENCY LIGHTING.
 13.2.9.3 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD NOT
 EXCEEDING
 300 AND USED EXCLUSIVELY FOR A PLACE OF WORSHIP SHALL
 NOT BE REQUIRED TO
 HAVE EMERGENCY LIGHTING
  
 7.9 EMERGENCY LIGHTING
 7.9.1 GENERAL.
 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE
 FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43
 (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS
 ADDRESSED IN
 SECTION 11.7
 (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS
 OF THIS CODE
 (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS
 (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF
 ENCLOSURES, FOR WHICH
 THE FOLLOWING ALSO APPLY:
 (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO
 INCLUDE A
 STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF
 ENCLO SURE MECHANICAL VENTILATION EQUIPMENT.
 (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED
 FOR THE
 STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER
 SUPPLY.
 (6) NEW SENSOR-RELEASE OF ELECTRICAL LOCKING SYSTEMS IN
 ACCORDANCE
 WITH 7.2.1.6.2
  
 7.9.1.2 FOR THE PURPOSES OF 7.9.1.1, EXIT ACCESS SHALL
 INCLUDE ONLY DES IGNATED STAIRS, AISLES, CORRIDORS,
 RAMPS, ESCALATORS, AND PASSAGEWAYS
 LEADING TO AN EXIT. FOR THE PURPOSES OF 7.9.1.1, EXIT
 DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS, RAMPS, AISLES,
 WALKWAYS, AND ESCALATORS
 LEADING TO A PUBLIC WAY
  
 PLEASE REVIEW AND CORRECT/PROVIDE.
  
  
  
 3) THERE ARE INDICATIONS OF THE INSTALLATION OF A FIRE
 ALARM SYSTEM.
  
 THE FIRE ALARM SYSTEM SHALL BE INSTALLED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
 4) SHEET E 10, GENERAL NOTE # 2. DUCT DETECTORS SHALL
 BE INSTALLED PER NFPA 90A AND CAN INITIATE SUPERVISORY
 PER NFPA 72
  
 PER NFPA 90 A , CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
 PER NFPA 72
  
 PER NFPA 72, 2013 ED
 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS.
 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO
 BE MONITORED AND A BUILDING FIRE ALARM SYSTEM IS
 INSTALLED, A DUCT DETECTOR ACTIVATION SIGNAL SHALL MEET
 THE REQUIREMENTS OF 21.7.4.
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL.
 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A
 CONSTANTLY ATTENDED LOCATION OR SUPERVISING STATION
 SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL.
 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM
 SIGNAL WHERE REQUIRED BY OTHER GOVERNING LAWS, CODES,
 OR STANDARDS.
  
 PLEASE PROGRAM ACCORDINGLY FOR SUPERVISORY ACTIVATION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709