| 2022-05-18 12:39:27 | ELECTRIC REVIEW FAILED |
| | 1) PLEASE PROVIDE LOCATIONS FOR ALL EQUIPMENT ON SITE |
| | PLAN, INCLUDING TRANSFER SWITCH, PANEL HMP AND PANEL A. |
| | NEC 215.5 FBC 107.2 |
| | 2) PLEASE PROVIDE CLARITY AND NEC CODES DETAILING |
| | COMPLIANCE AS TO THE FEEDERS FOR PANELS HMP AND PANEL |
| | A, ARE THESE TAPS FROM THE 300-AMP TRANSFER SWITCH AND |
| | MAIN BREAKER AT THE GARAGE? NEC 215.5 |
| | 3) PLEASE PROVIDE GROUNDING ELECTRODE SYSTEM DETAIL AT |
| | MAIN HOUSE AS PER NEC 250.32 |
| | 4) PLEASE PROVIDE AN ACCURATE ELECTRIC FLOOR PLAN |
| | DETAILING WHICH ELECTRICAL WIRING IS TO REMAIN AND |
| | WHICH IS TO BE MODIFIED, REPAIRED OR ADDED. FBC 107.2 |
| | 5) PLEASE DETAIL SHEET E-3 AND E-4 AS ELECTRIC |
| | DEMOLITION, IF THAT IS WHAT THE DRAWING DEPICTS. IT |
| | APPEARS, AS PER NOTE ALL TERMINAL DEVICES, IE |
| | RECEPTACLES SWITCHES ETC. ARE TO BE REMOVED. PLEASE |
| | PROVIDE CLARITY IN NOTES AS TO WHETHER THE ELECTRIC |
| | WIRING TO THESE DEVICES IS TO REMAIN. NOTE 1 AND 3 |
| | APPEAR REDUNDANT. FBC 107.2 |
| | 6) PLEASE PROVIDE CLARITY FOR NOTE 4 SHEET E-4. FBC |
| | 107.2 |
| | 7) PLEASE PROVIDE CLARITY OF THE LIMITED SCOPE ON SHEET |
| | E-4. FBC 107.2 |
| | 8) PLEASE DETAIL CORRECT DISCONNECT LOCATIONS FOR ALL |
| | CU AIR CONDITIONING UNITS TO SHOW COMPLIANCE WITH NEC |
| | 422.31(B) |
| | 9) PLEASE DETAIL COMPLIANCE WITH MEETING/CONFERENCE |
| | ROOMS FLOOR AND WALL RECEPTACLES. NEC 210.71 |
| | 10) PLEASE PROVE DETAIL TO SHOW COMPLIANCE WITH NEC |
| | 406.12 TAMPER RESISTANT RECEPTACLES |
| | 11) PLEASE PROVIDE A NOTE THAT FIRE ALARM, LOW VOLTAGE, |
| | SIGNS AND GENERATORS REQUIRE A SEPARATE PERMIT. |
| | |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS AND A NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |