Plan Review Notes
Plan Review Notes For Permit 22040875
Permit Number 22040875
Review Stop E
Sequence Number 1
Notes
Date Text
2022-05-18 12:39:27ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE LOCATIONS FOR ALL EQUIPMENT ON SITE
 PLAN, INCLUDING TRANSFER SWITCH, PANEL HMP AND PANEL A.
 NEC 215.5 FBC 107.2
 2) PLEASE PROVIDE CLARITY AND NEC CODES DETAILING
 COMPLIANCE AS TO THE FEEDERS FOR PANELS HMP AND PANEL
 A, ARE THESE TAPS FROM THE 300-AMP TRANSFER SWITCH AND
 MAIN BREAKER AT THE GARAGE? NEC 215.5
 3) PLEASE PROVIDE GROUNDING ELECTRODE SYSTEM DETAIL AT
 MAIN HOUSE AS PER NEC 250.32
 4) PLEASE PROVIDE AN ACCURATE ELECTRIC FLOOR PLAN
 DETAILING WHICH ELECTRICAL WIRING IS TO REMAIN AND
 WHICH IS TO BE MODIFIED, REPAIRED OR ADDED. FBC 107.2
 5) PLEASE DETAIL SHEET E-3 AND E-4 AS ELECTRIC
 DEMOLITION, IF THAT IS WHAT THE DRAWING DEPICTS. IT
 APPEARS, AS PER NOTE ALL TERMINAL DEVICES, IE
 RECEPTACLES SWITCHES ETC. ARE TO BE REMOVED. PLEASE
 PROVIDE CLARITY IN NOTES AS TO WHETHER THE ELECTRIC
 WIRING TO THESE DEVICES IS TO REMAIN. NOTE 1 AND 3
 APPEAR REDUNDANT. FBC 107.2
 6) PLEASE PROVIDE CLARITY FOR NOTE 4 SHEET E-4. FBC
 107.2
 7) PLEASE PROVIDE CLARITY OF THE LIMITED SCOPE ON SHEET
 E-4. FBC 107.2
 8) PLEASE DETAIL CORRECT DISCONNECT LOCATIONS FOR ALL
 CU AIR CONDITIONING UNITS TO SHOW COMPLIANCE WITH NEC
 422.31(B)
 9) PLEASE DETAIL COMPLIANCE WITH MEETING/CONFERENCE
 ROOMS FLOOR AND WALL RECEPTACLES. NEC 210.71
 10) PLEASE PROVE DETAIL TO SHOW COMPLIANCE WITH NEC
 406.12 TAMPER RESISTANT RECEPTACLES
 11) PLEASE PROVIDE A NOTE THAT FIRE ALARM, LOW VOLTAGE,
 SIGNS AND GENERATORS REQUIRE A SEPARATE PERMIT.
  
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS AND A NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER