Plan Review Notes
Plan Review Notes For Permit 22040863
Permit Number 22040863
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-12 14:01:541ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. HALL BATH V7 FRC P3108.2.1 - THE VENT CONNECTION IN
 THE HALL BATH MUST CONNECT WHERE ONLY ONE TRAP IS
 UPSTREAM.
  
 2. MASTER BATH V7 FRC P3108.2.1 - THE VENT CONNECTION
 IN THE MASTER BATH FOR THE TWO LAVS MUST CONNECT WHERE
 ONLY ONE TRAP IS UPSTREAM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  