| 2022-06-06 14:31:10 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC B 107.2.1 THE CITY OF WEST PALM BEACH IS NOT |
| | LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 150. PROVIDE |
| | A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| | USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 2. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT |
| | LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 128. SUBMIT |
| | FASTENER DENSITY CALCULATIONS PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER, |
| | REGISTERED ARCHITECT, OR REGISTERED ROOF CONSULTANT. |
| | 3. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| | CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| | HIP & RIDGE METAL TO BE USED. (FL5374-R6) |
| | 4. FBC B 107.3.4.1. SUBMITTED MIAMI-DADE COUNTY NOA |
| | NO.: 20-1124.07, MIAMI-DADE COUNTY NOA NO.: 21-0602.14, |
| | MIAMI-DADE COUNTY NOA NO.: 21-0420.04, PRODUCT APPROVAL |
| | FL12328-R9 ALONG WITH THE 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED HIP & RIDGE METAL & |
| | THE 2020 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE |
| | PROPOSED FLAT ROOF SYSTEM TO BE USED SHALL BE SUBMITTED |
| | TO THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE |
| | CHARGE WHO SHALL REVIEW THEM AND FORWARD THEM TO THE |
| | BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND |
| | FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE |
| | BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE |
| | INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN APPROVED BY THE BUILDING OFFICIAL. ALL APPLICABLE |
| | DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON |
| | THE PRODUCT APPROVAL DRAWINGS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |