| Plan Review Notes For Permit 22040806 |
| Permit Number |
22040806 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-07-18 16:09:32 | BASED ON THE SQUARE FOOTAGE SUBMITTED IN THE LATEST | | | OUTDOOR AIR CALCULATIONS AND FMC 403.3.1.1 AND ALSO | | | TABLE 403.3.1.1 THE OCCUPANCY DENSITY FOR A BAR IS | | | 100/1000SQ. FT. WHICH WOULD BE 65 TOTAL OCCUPANTS FOR | | | THIS SPACE. THE TOTAL OUTDOOR AIR REQUIRED FOR THSI 650 | | | SQ. FT. BAR WOULD BE 605 CFM. PLEASE PROVIDE THE | | | CORRECT OUTDOOR AIR CALCULATIONS FOR THIS BAR AREA. | | | HOPEFULLY THE SQ. FOOTAGE SUBMITTED IS THE NET | | | OCCUPIABLE FLOOR AREA THAT CAN BE USED ACCORDING TO | | | FOOT NOTE A OF TABLE 403.3.1.1. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|