2022-07-18 16:09:32BASED ON THE SQUARE FOOTAGE SUBMITTED IN THE LATEST
 OUTDOOR AIR CALCULATIONS AND FMC 403.3.1.1 AND ALSO
 TABLE 403.3.1.1 THE OCCUPANCY DENSITY FOR A BAR IS
 100/1000SQ. FT. WHICH WOULD BE 65 TOTAL OCCUPANTS FOR
 THIS SPACE. THE TOTAL OUTDOOR AIR REQUIRED FOR THSI 650
 SQ. FT. BAR WOULD BE 605 CFM. PLEASE PROVIDE THE
 CORRECT OUTDOOR AIR CALCULATIONS FOR THIS BAR AREA.
 HOPEFULLY THE SQ. FOOTAGE SUBMITTED IS THE NET
 OCCUPIABLE FLOOR AREA THAT CAN BE USED ACCORDING TO
 FOOT NOTE A OF TABLE 403.3.1.1.
  