Plan Review Notes
Plan Review Notes For Permit 22040806
Permit Number 22040806
Review Stop M
Sequence Number 2
Notes
Date Text
2022-06-30 06:22:48THE CALCULATIONS PRESENTED ARE FOR A LOBBY. THE OUTDOOR
 AIR CALCULATIONS REQUESTED WAS FOR THE NEWLY ADDED BAR
 AREA. THERE IS A BIG DIFFERENCE BETWEEN OUTDOOR AIR FOR
 A LOBBY AND A BAR. OUT DOOR AIR REQUIRED FOR 650 SQ FT
 OF BAR AREA WOULD BE 605 CFM'S. PLEASE PROVIDE THE
 OUTDOOR AIR CALCULATIONS FOR THE NEWLY ADDED BAR AREA.
 FMC 403.3.1.1 AND TABLE 403.3.1.1
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER