| Plan Review Notes For Permit 22040806 |
| Permit Number |
22040806 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-06-30 06:22:48 | THE CALCULATIONS PRESENTED ARE FOR A LOBBY. THE OUTDOOR | | | AIR CALCULATIONS REQUESTED WAS FOR THE NEWLY ADDED BAR | | | AREA. THERE IS A BIG DIFFERENCE BETWEEN OUTDOOR AIR FOR | | | A LOBBY AND A BAR. OUT DOOR AIR REQUIRED FOR 650 SQ FT | | | OF BAR AREA WOULD BE 605 CFM'S. PLEASE PROVIDE THE | | | OUTDOOR AIR CALCULATIONS FOR THE NEWLY ADDED BAR AREA. | | | FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|