Plan Review Notes
Plan Review Notes For Permit 22040754
Permit Number 22040754
Review Stop B
Sequence Number 2
Notes
Date Text
2022-07-14 11:23:47PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING REQUIRES THE GENERATOR
 TO WEIGH 850 LBS. THE 20KW KOHLER GENERATOR ONLY WEIGHS
 555 LBS. SUBMIT THE ENGINEERING FOR THE GENERATOR PAD
 THAT IS FOR THIS GENERATOR. FBC 107.2.1
  
 2) SPECIFY THE SIZE AND LOCATIONS OF THE FASTENERS THAT
 ARE REQUIRED TO ANCHOR THE GENERATOR TO THE SLAB. FBC
 107.2.1
  
 3) SEE THE COMMENTS UNDER THE SIGNATURE REVIEW.