| Date |
Text |
| 2022-04-27 11:35:24 | 04/27/22 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS A RECORD OF EXISTING |
| | LP TANK PERMITS BUT WITH NO INSPECTIONS FOR A PASS |
| | APPROVAL OF THE CURRENT SYSTEM. A SEARCH ON CITY |
| | RECORDS BACK TO 1995 HAS BEEN DONE AND THERE IS NO |
| | RECORD OF A PASSNG FOR THE INSTALLING AN LP TANK. A |
| | COMPLETE EVALUATION OF ALL GAS SYSTEMS AND EQUIPMENT |
| | MAY BE DONE ON THIS PERMIT BY THE PLUMBING INSPECTOR, |
| | AND IF NOT TO CODE, IT MAY NEED TO BE BOUT UP TO CODE |
| | COMPLIANCE AT THE OWNER'S EXPENSE. IF A PERMIT IS |
| | AVALABLE SHOWING A PASS OF THE SYSTEM THE REQUEST WILL |
| | NOT APPLY TO THIS PERMIT FOR COMPLIANCE. WHAT OTHER |
| | APPLIANCES/EQUIPMENT IS SUPPLIED BY THIS "EXISTING" |
| | TANK? PROVIDE ALL BTU LOADS AND THE TOTAL LOAD ON THE |
| | SYSTEM. IF THERE IS NO RECORD OF A PERMIT FOR THE LP |
| | TANK, THE TANK MUST BE INCLUDED IN A SEPARATE PERMIT |
| | FOR THIS SCOPE OF WORK PER THE WPB AMENDMENTS TO THE |
| | FBC S EC. 105.1. |
| | |
| | 2. WOULD YOU PLEASE SHOW A SHUTOFF VALVE AND HARD CAP |
| | FOR FUTURE POOL HEATER 2020 FBC RES. SEC. G2401.1.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |