Plan Review Notes
Plan Review Notes For Permit 22040737
Permit Number 22040737
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-05-17 12:51:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE NO INDICATIONS OF NOTIFICATION DEVICES IN
 THE RESTROOMS, BY DINING ROOMMAIN BLDG 1 FL (515 MEN)
  
 PLEASE REVIEW AND CORRECT PER NFPA 72, CH 18 OR PROVIDE
 A DETAILED NARRATIVE AND CODE REFERENCES FOR NOT
 PROVIDING NOTIFICATION IN THESE SPACES.
  
  
 2) THERE ARE NO INDICATIONS OF NOTIFICATION DEVICES IN
 THE RESTROOM BY MEETING ROOM, MAIN BLDG 1 FL (503
 WOMEN)
  
 PLEASE REVIEW AND CORRECT PER NFPA 72, CH 18 OR PROVIDE
 A DETAILED NARRATIVE AND CODE REFERENCES FOR NOT
 PROVIDING NOTIFICATION IN THESE SPACES.
  
  
 3) CORRECT ALL CALULATIONS RELATED TO ANY ADDED DEVICES
 PER ABOVE COMMENTS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  