| Plan Review Notes For Permit 22040737 |
| Permit Number |
22040737 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-17 12:51:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS OF NOTIFICATION DEVICES IN | | | THE RESTROOMS, BY DINING ROOMMAIN BLDG 1 FL (515 MEN) | | | | | | PLEASE REVIEW AND CORRECT PER NFPA 72, CH 18 OR PROVIDE | | | A DETAILED NARRATIVE AND CODE REFERENCES FOR NOT | | | PROVIDING NOTIFICATION IN THESE SPACES. | | | | | | | | | 2) THERE ARE NO INDICATIONS OF NOTIFICATION DEVICES IN | | | THE RESTROOM BY MEETING ROOM, MAIN BLDG 1 FL (503 | | | WOMEN) | | | | | | PLEASE REVIEW AND CORRECT PER NFPA 72, CH 18 OR PROVIDE | | | A DETAILED NARRATIVE AND CODE REFERENCES FOR NOT | | | PROVIDING NOTIFICATION IN THESE SPACES. | | | | | | | | | 3) CORRECT ALL CALULATIONS RELATED TO ANY ADDED DEVICES | | | PER ABOVE COMMENTS. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|