Plan Review Notes
Plan Review Notes For Permit 22040709
Permit Number 22040709
Review Stop E
Sequence Number 1
Notes
Date Text
2022-06-09 15:02:3622040709
 ELECTRIC REVIEW FAILED
 1) IT APPEARS SECONDARY CONDUCTORS FOR 15KVA
 TRANSFORMERS ARE SIZED INCORRECTLY. SECONDARY COPPER
 CONDUCTORS SIZED TO NOT LESS THAN THE SECONDARY
 PROTECTION DEVICE RATING [240.21(C)] 75?C TERMINALS
 [110.14(C)(1)(A)(2)] PER TABLE 310.15(B)(16). PLEASE
 CORRECT AS APPLICABLE
 2) IT APPEARS PANEL BOARD FED FROM PANEL BOARD H4 VIA
 15 KVA TRANSFORMER DETAILS THE INCORRECT NOMENCLATURE
 ?PANELBOARD A?, IT APPEARS THIS SHOULD BE LABELED
 PANELBOARD D. PLEASE CORRECT AS APPLICABLE
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved