| Date |
Text |
| 2022-05-10 13:10:14 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22040691 |
| | ADD: 801 S OLIVE AVE # 1603 |
| | CONT: ENTRUSTED |
| | TEL: 561-324-4088 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MAY 10TH/ 2022 |
| | ACTION: DENIED |
| | |
| | 1) 5/17/2022, NOT APPLICABLE, BUILDING OFFICIAL. THE |
| | PERMIT APPLICATION STATES THE VALUE OF THE PROJECT IS |
| | $29,519.29 DOLLARS. PROJECT $25,000.00 AND GREATER |
| | REQUIRE A DESIGN PROFESSIONAL TO CREATE THE PLANS. SEE |
| | FL STATUTE 481. 481.229 EXCEPTIONS; EXEMPTIONS FROM |
| | LICENSURE (1) (C) ANY OTHER TYPE OF BUILDING COSTING |
| | LESS THAN $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR |
| | OTHER BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT |
| | THE SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE |
| | REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45. |
| | |
| | 2) NOT APPLICABLE, ON PLANS. 2020 FBC-B 2509.2 BASE FOR |
| | TILE. MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND |
| | SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER |
| | AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND |
| | INSTALLED IN ACCORDANCE WITH MANUFACTURER?S |
| | RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C840 AND THE MANUFACTURE?S |
| | RECOMMENDATIONS. |
| | |
| | 3) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| | COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| | SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| | HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| | |
| | 4) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS |
| | IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO |
| | BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR |
| | SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION |
| | CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE |
| | FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE |
| | WITH THE 2020 FBC-B SECTION 714.5.1.2. |
| | THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY |
| | A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN |
| | ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL |
| | HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT |
| | NOT LESS THAN THE REQUIRED RATING OF THE FLOOR |
| | PENETRATED. |
| | |
| | 6) TUB ENCLOSURE WALLS AND OR SHOWER WALLS. TUB |
| | ENCLOSURE WALLS AND OR SHOWER WALLS WHICH ARE ALSO |
| | TENANT SEPARATION WALL WHICH WILL ALSO NEED TO SHOW |
| | COMPLIANCE WITH SECTION 420.2 SEPARATION WALLS AND FIRE |
| | PARTITIONS IN ACCORDANCE WITH SECTION 708 OF THE 2020 |
| | FBC-BUILDING CODE. |
| | |
| | 7) FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR |
| | TILE, STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE |
| | FLOORING AND WOOD FLOORING ALL NEED TO HAVE HAD THE |
| | SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE |
| | FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED |
| | UNDER EACH OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR |
| | ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 7A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 7B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 7C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 8) FAIR HOUSING GUIDELINES. FAIR HOUSING ACT DESIGN AND |
| | CONSTRUCTION REQUIREMENTS. FOR PURPOSES OF THIS |
| | SECTION, A COVERED MULTIFAMILY DWELLING SHALL BE DEEMED |
| | TO BE DESIGNED AND CONSTRUCTED FOR FIRST OCCUPANCY ON |
| | OR BEFORE MARCH 13, 1991, IF THEY ARE OCCUPIED BY THAT |
| | DATE OR IF THE LAST BUILDING PERMIT OR RENEWAL THEREOF |
| | FOR THE COVERED MULTIFAMILY DWELLINGS IS ISSUED BY A |
| | STATE, COUNTY OR LOCAL GOVERNMENT ON OR BEFORE JANUARY |
| | 13, 1990. |
| | FAIR HOUSING LETTER AS AN ALTERNATE METHOD. SEE LETTER: |
| | PROJECT ADDRESS: ______________________________________ |
| | _____________________ |
| | PERMIT NUMBER: ________________________ |
| | THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE |
| | PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS |
| | OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER |
| | AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF |
| | SALE IF SO REQUESTED BY THE BUYER. |
| | |
| | SIGNATURE OF DESIGNER: ______________________________ |
| | PRINTED NAME OF DESIGNER: ___________________________ |
| | |
| | SIGNATURE OF OWNER: ________________________________ |
| | PRINTED NAME OF OWNER: _____________________________ |
| | NOTARY FOR OWNER?S SIGNATURE: |
| | STATE OF FLORIDA, COUNTY OF PALM BEACH |
| | THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME |
| | THIS _____ DAY OF ________, 20__ BY |
| | ___________________________ WHO IS PERSONALLY KNOWN TO |
| | ME OR WHO HAS PRODUCED: ___________________________ AS |
| | IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH. |
| | NOTARY SIGNATURE ___________________________________ |
| | NOTARY PRINTED NAME ________________________________ |
| | |
| | 9) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |