2022-05-03 16:48:011ST REVIEW FMC
 PERMIT: 22040689
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEPARATE THE REFRIGERATION FROM ALL OTHER
 PERMITS. THIS SHOULD BE A SEPARATE PERMIT WITH THE
 ENTIRE REFRIGERATION SYSTEM DESIGN SUBMITTED TOGETHER.
 THIS PERMIT APPLICATION STATES IT IS FOR CASE
 EXCHANGES, SHELVING CHANGES. THE REFRIGERATION THAT IS
 ON THESE DRAWINGS INDICATE THIS IS MORE THAN CASE
 EXCHANGES. WHEN SUBMITTING THE REQUIRED REFRIGERATION
 PERMIT AND DOCUMENTS FOR REVIEW PLEASE INCLUDE A
 COMPLETE DESIGN INCLUDING THE LOCATIONS OF THE
 REFRIGERATION MACHINERY AND THE REQUIREMENTS OF FMC
 1102.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  