| 2022-05-03 16:48:01 | 1ST REVIEW FMC | | | PERMIT: 22040689 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SEPARATE THE REFRIGERATION FROM ALL OTHER | | | PERMITS. THIS SHOULD BE A SEPARATE PERMIT WITH THE | | | ENTIRE REFRIGERATION SYSTEM DESIGN SUBMITTED TOGETHER. | | | THIS PERMIT APPLICATION STATES IT IS FOR CASE | | | EXCHANGES, SHELVING CHANGES. THE REFRIGERATION THAT IS | | | ON THESE DRAWINGS INDICATE THIS IS MORE THAN CASE | | | EXCHANGES. WHEN SUBMITTING THE REQUIRED REFRIGERATION | | | PERMIT AND DOCUMENTS FOR REVIEW PLEASE INCLUDE A | | | COMPLETE DESIGN INCLUDING THE LOCATIONS OF THE | | | REFRIGERATION MACHINERY AND THE REQUIREMENTS OF FMC | | | 1102. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|