| Plan Review Notes For Permit 22040686 |
| Permit Number |
22040686 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-03 15:56:47 | INTERIOR DEMO | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) A UNITY OF TITLE IS REQUIRED TO REMOVE THE TENNANT | | | SEPARATION WALL. FBC 420.2 SEPARATION WALLS. | | | WALLS SEPARATING DWELLING UNITS IN THE SAME BUILDING, | | | WALLS SEPARATING SLEEPING UNITS IN THE SAME BUILDING | | | AND WALLS SEPARATING DWELLING OR SLEEPING UNITS FROM | | | OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME | | | BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN | | | ACCORDANCE WITH SECTION 708. | | | |
|