Plan Review Notes
Plan Review Notes For Permit 22040674
Permit Number 22040674
Review Stop B
Sequence Number 2
Notes
Date Text
2022-05-28 06:46:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WIND DESIGN CRITERIA HAS BEEN CHANGED TO EXPOSURE C,
 BUT DESIGN PRESSURES PROPOSED ARE NOT CLEAR. DESIGN
 PRESSURES WHICH APPEAR TOO LOW ARE LISTED, THEN A
 STATEMENT ON THE PLAN "MULTIPLIER 1.21". DOES THAT MEAN
 THAT A MULTIPLIER OF 1.21 WAS APPLIED, OR YOU ARE
 PROPOSING THAT SOMEONE ELSE DO THE MATH TO STATE WHAT
 THE DESIGN PRESSURES ARE?
  
 YOU CAN STATE HOW YOU DERIVED THE DESIGN PRESSURES, BUT
 THE PRESSURES SHOULD BE DETERMINED BY THE INDIVIDUAL
 TAKING RESPONSIBILITY FOR THE DESIGN, FBC 107. REVISE
 SO REQUIRED DESIGN PRESSURES ARE CLEAR. IF THEY APPEAR
 TOO LOW, CALCULATIONS WILL BE REQUIRED.
  
 2. NEW COMMENT - ON THE ROOF PLAN, INCLUDE THE PRINTED
 NAME AND SIGNATURE OF THE INDIVIDUAL TAKING
 RESPONSIBILITY FOR THE DESIGN, FBC 107.
  
 3. NEW COMMENT - A NEW METAL ROOF NOA WAS UPLOADED.
 PLEASE COORDINATE WITH [email protected] TO
 REMOVE DOCUMENTS THAT YOU DO NOT WANT REVIEWED AND
 ISSUED, FBC 107.
  
  
  
  
  
  