2022-04-20 13:04:58PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 HYDROSTATIC TETS. ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT 200 PSI (13.8 BAR) AND SHALL
 MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2 HOURS.
  