| Plan Review Notes For Permit 22040625 |
| Permit Number |
22040625 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-07-22 09:56:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | DETAIL NAMED "REID - WALL DETAIL" HAS BEEN LOCKED (WILL | | | NOT ISSUE, WILL BE DELETED). THIS REVIEW IS FOR THE | | | WALL DETAIL "SITE WALL-SK-1". NUMBERING REMAINS THE | | | SAME AS PREVIOUS TWO COMMENT LISTS, COMMENTS ADDRESSED | | | HAVE BEEN REMOVED. | | | | | | 1. THE STRUCTURAL DETAIL IS TO INCLUDE WIND DESIGN | | | CRITERIA. FBC R 301. | | | | | | 3. PROVIDE A SITE PLAN THAT SHOWS THE FOOTING RELATIVE | | | TO THE PROPERTY LINE, FBC 107. | | | | | | NOT ADDRESSED. THE SITE PLAN GRAPHICALLY SHOWS THE WALL | | | OVER THE PROPERTY LINE. FOOTER IS NOT ECCENTRIC SO THE | | | WAY IT IS DESIGNED, THE FOOTER WILL BE INSTALLED ON | | | CITY AND NEIGHBORING PROPERTY. | | | | | | 5. THE WALL IS SHOWN AS CONTINUOUS. HOW WILL OCCUPANTS | | | EXIT THE PROPERTY IN THE EVENT OF AN EMERGENCY? HOW | | | WILL OCCUPANTS ACCESS THE PROPERTY? FBC 107. SCOPE OF | | | WORK IS NOT CLEAR. | | | |
|