| Plan Review Notes For Permit 22040599 |
| Permit Number |
22040599 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-05 07:25:09 | 2ND REVIEW FMC | | | PERMIT: 22040599 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE AN EXHAUST FAN IN THE MASTER SHOWER AND TUB | | | AREA. FRC R303.3 | | | | | | 2) PROVIDE THE ENERGY CALS AND MECHANICAL EQUIPMENT | | | SIZING CALCULATIONS FOR THE CONDITIONED SPACE ABOVE THE | | | GARAGE THAT WAS SUBMITTED AS A CHANGE THIS CYCLE. FBC | | | 107.2.1 | | | | | | | | | THE ENERGY CALCULATIONS AND MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS WERE NOT SUBMITTED IN THIS SUBMITTAL: | | | | | | SEE PREVIOUS COMMENTS BELOW, STILL WAITING ON THE | | | ENERGY CALS AND THE MECHANICAL EQUIPMENT SIZING CALCS. | | | | | | 1ST REVIEW FMC | | | PERMIT: 22040599 | | | | | | | | | 1) PLEASE SUBMIT THE ENERGY CALCULATIONS. FEC | | | 101.5.1.1.2 | | | | | | 2) PLEASE SUBMIT THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC R403.7.1 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|