Plan Review Notes
Plan Review Notes For Permit 22040597
Permit Number 22040597
Review Stop G
Sequence Number 2
Notes
Date Text
2023-02-13 10:41:472ND REVIEW FBC-2020 RES. GAS
 PERMIT- 22040597
 2/13/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED 1ST REVIEW COMMENTS
 ARE LISTED BELOW WITH ADDITIONAL NOTES. PLEASE CONTACT
 ME IF YOU HAVE QUESTIONS.
  
 1) GAS RISER: ADDITIONAL INFORMATION REQUIRED ON THE
 DRAWING- CHAPTER 24 FBC RES.
  
 A) SHOW THE GAS SYSTEM PRESSURE- 2 PSI OR LOW
 PRESSURE..
 B) SHOW A REGULATOR AND SHUT OFF VALVE AT WATER HEATER.
 C) SHOW THE TYPE AND SIZE OF MAIN SUPPLY PIPE FROM THE
 METER TO THE PE RISER.
 D) SHOW THE TYPE AND SIZE OF SUPPLY PIPE FROM THE
 REGULATOR AT THE POOL HEATER TO THE HEATER.
 E) SHOW PIPE CONNECTION AT THE METER TO EXISTING
 APPLIANCES AND PROVIDE THE TOTAL BTU LOAD OF THE
 EXISTING APPLIANCES AND THE NEW POOL HEATER.
  
 2) PROVIDE A BASIC SITE PLAN THAT SHOWS THE LOCATIONS
 OF THE METER, POOL HEATER, AND UNDERGROUND PIPING RUN-
 SEC. 107.2.1 WPB. PLEASE INCLUDE THE INSTALLATION
 CLEARANCES FOR THE POOL HEATER- MINIMUM 4FT. FROM
 OPENINGS INTO THE BUILDING- SEC. G2427.8 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy