| 2022-06-09 13:31:11 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22040585 625 N FLAGLER DR # 400 |
| | |
| | 2ND REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. PLEASE NOTE, THE LAST CLOSED PERMIT FOR THE ADDRESS |
| | IS MASTER 17120950 WITH A REVISION PERMIT 18090893. |
| | THERE ARE TWO THINGS TO NOTE. |
| | |
| | ***A) THE FIRST IS THAT THE ACCESSIBLE WATER CLOSETS ON |
| | THE NEW DRAWINGS ARE REPOSITIONED (90 DEGREES) FROM |
| | THOSE ON THE CLOSED PERMIT AND ARE LOCATED ADJACENT TO |
| | THE WET WALL SEPARATING THE TWO BATHROOMS. WE ARE |
| | REQUIRED TO LOOK AT THE WORK IN THE HANDICAPPED STALLS |
| | AS NEW WORK. |
| | PER WPB FBC 107.2.1, PROVIDE PLAN ELEVATION DETAILS OF |
| | THE STALLS SHOWING THE FOLLOWING: |
| | ****11A) MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 603.3. |
| | SECOND REQUEST-TO BE CLEAR, PLEASE CLARIFY ON PLANS |
| | THAT DIMENSION IS TO THE REFLECTING SURFACE OF THE |
| | MIRROR. |
| | |
| | ***B) THE SECOND THING TO NOTE IS THE "EXISTING" |
| | SANITARY PIPING ON THE NEW DRAWINGS IS CONFIGURED |
| | DIFFERENTLY FROM THE CLOSED PERMIT PLANS TO ACCOMMODATE |
| | THE ACCESSIBLE WATER CLOSETS. WE ARE REQUIRED TO LOOK |
| | AT THE SANITARY PIPING FROM THE MOST UPSTREAM WATER |
| | CLOSET TO THE MOST DOWNSTREAM WATER CLOSET AS NEW. |
| | PLEASE SEE THE FOLLOWING: |
| | ****1B) SECOND REQUEST: NO RESPONSE- P3-00 SANITARY |
| | RISER: PROVIDE A 2 INCH DRY VERTICAL CIRCUIT VENT |
| | CONNECTED TO THE HORIZONTAL BRANCH BETWEEN THE TWO |
| | UPSTREAM WATER CLOSETS TO COMPLY WITH FBC PL 914.2 |
| | |
| | |
| | 2. SECOND REQUEST: NO RESPONSE-PLEASE NOTE WHERE SINKS |
| | ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER THAN |
| | ONE, OF EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM OR |
| | SPACE SHALL COMPLY WITH 606 PER FBC ACC 212.3. |
| | ***A) PER WPB FBC 107.2.1, PROVIDE ELEVATION FOR SINKS |
| | S-2, S-3 AND S-4 SHOWING COMPLIANCE WITH FBC ACC 606.3, |
| | 306.2 AND 306.3. |
| | ***B) PER WPB FBC 107.2.1, SHOW CLEAR FLOOR SPACES FOR |
| | SINKS S-2, S-3 AND S-4 COMPLYING WITH FBC ACC SECTION |
| | 305. |
| | |
| | |
| | 3. COMPLIED |
| | |
| | |
| | 4. PARTIALLY COMPLIED: PER WPB FBC 107.2.1, PROVIDE |
| | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUALS FOR |
| | WATER HEATER, RECIRC PUMP. RESPONSE: PROVIDE DEFERRED |
| | SUBMITTALS |
| | |
| | |
| | 5. PARTIALLY COMPLIED: PER WPB FBC 107.2.1, PROVIDE |
| | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUALS FOR |
| | OWNER SUPPLIED EQUIPMENT. RESPONSE: PROVIDE DEFERRED |
| | SUBMITTALS |
| | |
| | |
| | 6. COMPLIED |
| | |
| | |
| | 7. PARTIALLY COMPLIED: P0-00/PLUMBING CONSTRUCTION |
| | NOTES: |
| | ***D) SECOND REQUEST: RE: SECTION 22000. PER WPB FBC |
| | 107.2.1, PROVIDE SECTION 22000 BY UPLOADING TO PROJECT |
| | DOCS/SUPPORTING DOCUMENTS ON THE NEXT SUBMITTAL. |
| | COULD NOT FIND IN PROJECT DOCS. PLEASE RESUBMIT |
| | ***E) RE: SECOND REQUEST: SECTION 27000. PER WPB FBC |
| | 107.2.1, PROVIDE SECTION 27000 BY UPLOADING TO PROJECT |
| | DOCS/SUPPORTING DOCUMENTS ON THE NEXT SUBMITTAL. |
| | COULD NOT FIND IN PROJECT DOCS. PLEASE RESUBMIT |
| | |
| | |
| | COMMENTS 8 THROUGH 15. COMPLIED |
| | |
| | |
| | 16. PARTIALLY COMPLIED: P5-00/JS-1/TMV/EYEWASH-DRENCH |
| | HOSE: PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING; |
| | ***D) PROVIDE MANUFACTURER'S SPECIFICATION/INSTALLATION |
| | MANUAL FOR TMV AND EYEWASH/DRENCH HOSE. RESPONSE: |
| | PROVIDE DEFERRED SUBMITTALS |
| | |
| | |
| | 17. PARTIALLY COMPLIED: P5-00/SS-1/TMV/RECESSED |
| | EYEWASH-DRENCH: PER WPB FBC 107.2.1, PROVIDE THE |
| | FOLLOWING; |
| | ***D) PROVIDE MANUFACTURER'S SPECIFICATION/INSTALLATION |
| | MANUAL FOR TMV AND RECESSED EYEWASH/DRENCH. RESPONSE: |
| | PROVIDE DEFERRED SUBMITTALS |
| | |
| | |
| | 19.PARTIALLY COMPLIED: RATED WALL PENETRATIONS HAVE |
| | BEEN PROVIDED. PER WPB FBC 107.2.1, PROVIDE APPLICABLE |
| | RATED FLOOR DETAILS FOR PLUMBING FLOOR PENETRATIONS |
| | COMPLYING WITH THE REQUIREMENTS OF FBC CHAPTER 7. |
| | |
| | |
| | NEW COMMENT: |
| | 1A. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE |
| | AS DEFERRED SUBMITTALS, MANUFACTURER?S |
| | SPECIFICATION/INSTALLATION MANUAL FOR THE PLUMBING |
| | FIXTURES, KITCHEN EQUIPMENT AND BACKFLOW PREVENTERS AS |
| | INDICATED ON PLAN SHEET P0.1. SUBMITTAL SHALL BE |
| | SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL |
| | INSPECTION. PROCEED AT YOUR OWN RISK. |
| | 1B. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE |
| | ON THE PLANS A LIST OF DEFERRED SUBMITTALS TO INCLUDE |
| | THE FOLLOWING: |
| | WATER HEATER |
| | RECIRCULATING PUMP |
| | OWNER SUPPLIED EQUIPMENT |
| | THERMAL MIXING VALVES |
| | EYEWASH/DRENCH HOSE |
| | RECESSED EYEWASH/DRENCH |
| | BACKFLOW PREVENTER(S) |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |