Notes
Date Text
2022-05-12 16:36:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99-18 - SEE P0-00/GENERAL PLUMBING NOTE 2-CODES
 AND STANDARDS/NOTE 16 PIPE SPEC
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22040585 625 N FLAGLER DR # 400
 1ST REVIEW
  
 MEDGAS COMMENTS: DENIED
  
 1.PER WPB FBC 107.2.1, PLEASE NOTE ANY AND ALL
 APPLICABLE STANDARDS FOR THE SYSTEM, INCLUDING THE
 INSTALLATION.
  
 2. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUALS FOR THE FOLLOWING:
 ***A) E8-CO2 INCLUDING BUT NOT LIMITED TO CHANGE OVER
 MANIFOLD, ALARM, HEADERS, REGULATORS, BALL VALVES,
 CHECK VALVES, FLEXIBLE CYLINDER CONNECTORS
 ***B) E9-CO2 INCUBATOR
 ***C) POU REGULATOR FOR E9 CO2 INCUBATOR
  
 3. P0-00/GENERAL PLUMBING NOTE 2: CALLS FOR TYPE L
 COPPER TUBING CLEANED AND PURGED FOR OXYGEN SERVICE
 (ASTM B819 ACR/OXY), NITROGEN PURGED AND SILVER BRAZED
 IN ACCORDANCE WITH NFPA 99. PER WPB FBC 107.2.1,
 PROVIDE SPECIFICATION FOR FITTINGS AND VALVES IN THE
 SYSTEM AND INSTALLATION PROCEDURES.
  
 4.PER WPB FBC 107.2.1, REQUIRE DOCUMENTATION ON ALL
 PIPE, VALVES AND FITTINGS PER NFPA 99-18 SECTION
 5.1.10.1.2 AND 5.1.10.1.4. DOCUMENTATION SHALL BE ON
 SITE FOR INSPECTION.
  
 5. PER WPB FBC 107.2.1, REQUIRE BRAZING TECHNICIANS TO
 BE QUALIFIED AND CERTIFIED IN ACCORDANCE WITH NFPA
 99-18 SECTION 5.1.10.11.11.1. DOCUMENTATION SHALL BE ON
 SITE FOR INSPECTION.
  
 6. PER WPB FBC 107.2.1, PROVIDE STANDARD FOR AND
 PROVIDE VALVE ID/SYSTEM IDENTIFICATION/COLOR CODING
 SPECIFICATION.
  
 7.PER WPB FBC 107.2.1, PROVIDE WALL SUPPORT
 STRUCTURE(S) FOR THE VERTICAL PIPING.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved