| 2022-05-12 16:36:59 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | NFPA 99-18 - SEE P0-00/GENERAL PLUMBING NOTE 2-CODES |
| | AND STANDARDS/NOTE 16 PIPE SPEC |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22040585 625 N FLAGLER DR # 400 |
| | 1ST REVIEW |
| | |
| | MEDGAS COMMENTS: DENIED |
| | |
| | 1.PER WPB FBC 107.2.1, PLEASE NOTE ANY AND ALL |
| | APPLICABLE STANDARDS FOR THE SYSTEM, INCLUDING THE |
| | INSTALLATION. |
| | |
| | 2. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUALS FOR THE FOLLOWING: |
| | ***A) E8-CO2 INCLUDING BUT NOT LIMITED TO CHANGE OVER |
| | MANIFOLD, ALARM, HEADERS, REGULATORS, BALL VALVES, |
| | CHECK VALVES, FLEXIBLE CYLINDER CONNECTORS |
| | ***B) E9-CO2 INCUBATOR |
| | ***C) POU REGULATOR FOR E9 CO2 INCUBATOR |
| | |
| | 3. P0-00/GENERAL PLUMBING NOTE 2: CALLS FOR TYPE L |
| | COPPER TUBING CLEANED AND PURGED FOR OXYGEN SERVICE |
| | (ASTM B819 ACR/OXY), NITROGEN PURGED AND SILVER BRAZED |
| | IN ACCORDANCE WITH NFPA 99. PER WPB FBC 107.2.1, |
| | PROVIDE SPECIFICATION FOR FITTINGS AND VALVES IN THE |
| | SYSTEM AND INSTALLATION PROCEDURES. |
| | |
| | 4.PER WPB FBC 107.2.1, REQUIRE DOCUMENTATION ON ALL |
| | PIPE, VALVES AND FITTINGS PER NFPA 99-18 SECTION |
| | 5.1.10.1.2 AND 5.1.10.1.4. DOCUMENTATION SHALL BE ON |
| | SITE FOR INSPECTION. |
| | |
| | 5. PER WPB FBC 107.2.1, REQUIRE BRAZING TECHNICIANS TO |
| | BE QUALIFIED AND CERTIFIED IN ACCORDANCE WITH NFPA |
| | 99-18 SECTION 5.1.10.11.11.1. DOCUMENTATION SHALL BE ON |
| | SITE FOR INSPECTION. |
| | |
| | 6. PER WPB FBC 107.2.1, PROVIDE STANDARD FOR AND |
| | PROVIDE VALVE ID/SYSTEM IDENTIFICATION/COLOR CODING |
| | SPECIFICATION. |
| | |
| | 7.PER WPB FBC 107.2.1, PROVIDE WALL SUPPORT |
| | STRUCTURE(S) FOR THE VERTICAL PIPING. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |