| Plan Review Notes For Permit 22040565 |
| Permit Number |
22040565 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-19 13:30:48 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | EXISTING FEEDERS DO NOT MEET THE REQUIREMENTS OF | | | 310.15(B)(7) 3/0 NOT FEEDING THE ENTIRE LOAD. | | | | | | PLEASE SUBMIT A COST BREAKDOWN OR A SIGNED CONTRACT FOR | | | THE INSTALLATION OF THE GENERATOR. | | 2022-05-04 11:25:32 | SIGNED "IN" BY MISTAKE |
|