| Plan Review Notes For Permit 22040563 |
| Permit Number |
22040563 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-11-07 12:45:37 | 3RD GAS REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. DONE | | | | | | 2. ALSO TO BE NOTED: YOUR QUOTE FROM THE NFPA 54 IN | | | REFERENCE TO DRYERS "EXCEPTION #2" SHOULD BE CLARIFIED | | | TO SAY THAT DRYERS ARE NOT INCLUDED IF THEY ARE | | | PROVIDED WITH MAKE UP AIR IN ACCORDANCE WITH 10.4.3. | | | ALSO TO BE NOTED, THE NFPA 54 IS NOT APPLICABLE AS IT | | | SHOULD REFERENCE THE FLORIDA FUEL GAS CODE AND USE CODE | | | SECTION G2407.1 FROM THE 2020 RESIDENTIAL BUILDING | | | CODE. DRYERS ARE TO BE SUPPLIED WITH MAKE UP AIR IN | | | ACCORDANCE WITH G2439.5. | | | | | | 3. NEW COMMENT - 2020 FRC G2439.5 (614.6) MAKEUP AIR - | | | PLEASE DETAIL THE MAKE UP AIR REQUIRED FOR THE DRYER. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 |
|