2022-11-03 15:47:052ND GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2439.5 (614.6) YOUR COMBUSTION AIR
 CALCULATIONS ARE NOT ACCURATE. ROOM VOLUME AT 10 TIMES
 7 TIMES 8 DOES NOT EQUAL 3920. IT EQUALS 560. IN WHICH
 CASE MAKE UP AIR IS REQUIRED.
  
 2. ALSO TO BE NOTED: YOUR QUOTE FROM THE NFPA 54 IN
 REFERENCE TO DRYERS "EXCEPTION #2" SHOULD BE CLARIFIED
 TO SAY THAT DRYERS ARE NOT INCLUDED IF THEY ARE
 PROVIDED WITH MAKE UP AIR IN ACCORDANCE WITH 10.4.3.
 ALSO TO BE NOTED, THE NFPA 54 IS NOT APPLICABLE AS IT
 SHOULD REFERENCE THE FLORIDA FUEL GAS CODE AND USE CODE
 SECTION G2407.1 FROM THE 2020 RESIDENTIAL BUILDING
 CODE. DRYERS ARE TO BE SUPPLIED WITH MAKE UP AIR IN
 ACCORDANCE WITH G2439.5.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  