| 2022-11-30 10:59:45 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II/INSPECTOR |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | NFIP REVIEW DENIED: |
| | |
| | 1. FBC B 107.2.1, PROVIDE THE PRODUCT APPROVAL FOR THE |
| | MASTER FLOW FLOOD VENTS THAT ARE INDICATED ON PLAN |
| | SHEET A-101. |
| | 2. FBC R 322.2.2.1, AN ADDITIONAL FLOOD VENT IS |
| | REQUIRED AT THE REAR WALL OF GARAGE (2 OPENINGS ON |
| | DIFFERENT SIDES OF ENCLOSED AREA). PLEASE SHOW ALL |
| | FLOOD OPENINGS ON PLAN SHEETS. |
| | 3. SECTION A-4 OF THE ELEVATION CERTIFICATE, PLEASE |
| | CLARIFY AS IT APPEARS THAT THIS SHOULD BE ATTACHED |
| | GARAGE IN-LIEU OF NON-RESIDENTIAL. |
| | 4. SECTION A-9(B) OF THE ELEVATION CERTIFICATE, IT |
| | APPEARS THAT THE NUMBER OF PERMANENT FLOOD OPENINGS |
| | SHOULD BE (4) IN-LIEU OF (0). PLEASE ADJUST ELEVATION |
| | CERTIFICATE. |
| | 5. SECTION A-9(C) OF THE ELEVATION CERTIFICATE, IT |
| | APPEARS THAT THE TOTAL NET AREA OF THE FLOOD OPENINGS |
| | SHOULD NOT BE (0). THIS NUMBER SHOULD BE 4X THE NET |
| | AREA OF EACH FLOOD OPENING. PLEASE ADJUST ELEVATION |
| | CERTIFICATE. |
| | 6. SECTION D (COMMENTS) OF THE ELEVATION CERTIFICATE; |
| | PLEASE CLARIFY WHAT EQUIPMENT AND LOCATION OF EQUIPMENT |
| | PER INDICATIONS IN SECTION C2 E. ALSO CLARIFY "LARC |
| | 3.7' IN THIS SECTION D COMMENTS. |
| | |
| | |
| | |
| | NOTE: ADDITIONAL INFORMATION WILL BE REQUIRED WHEN |
| | SUBMITTING THE ELEVATION CERTIFICATE FOR THE "BUILDING |
| | UNDER CONSTRUCTION" AND "FINISHED CONSTRUCTION" PHASES. |