 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1 & FBC R 401.3, PROVIDE A DRAINAGE
 PLAN INDICATING THE DIRECTIONS OF SURFACE WATER FLOW.
 2.) FBC B 107.2.1 & FBC B 107.2.6, PROVIDE A SURVEY &
 SITE PLAN COMPLETE WITH ELEVATIONS (EXISTING &
 PROPOSED) AND SET BACKS MEASUREMENTS.
 3.) FBC B 107.2.1, PROVIDE APPROVED REVIEW STAMPS BY
 THE DESIGNER OF RECORD ON ALL PRODUCT APPROVALS.
 4.) FBC B 107.2.1 & FBC R 703.7.3, THE WOOD FRAMED
 TRUSS GABLE END AREAS ARE TO MEET THE REQUIREMENTS OF
 WATER RESISTIVE BARRIERS (TYPICALLY 2-LAYERS OF
 MOISTURE BARRIER BETWEEN SHEATHING AND LATH). PLEASE
 SHOW ON PLANS.
  
  