Plan Review Notes
Plan Review Notes For Permit 22040556
Permit Number 22040556
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-04-26 13:35:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION ON THE APPLICATION OF
 "REPLACE TILE"
  
 TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT
 CERAMIC/PORCELAIN/MARBLE/CEMENT
 IT CAN BE VINYL/LAMINATE ETC AND IS MANUFACTURED FROM
 AROUND THE WORLD AND NOT ALL ARE
 TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD PLEASE PROVIDE THE TILE TYPE
 I.E. CERAMIC, MARBLE, TERRACOTTA, STONE
 WHICH WOULD NOT REQUIRE A SPEC SHEET.
  
 FOR OTHER TYPE OF TILE PRODUCT TYPE I.E. VINYL OR VINYL
 PLANKS, CORK, WOOD PLEASE PROVIDE
 THE MANUFACTURE PRODUCT FLAME SPREAD/PRODUCT SAFETY
 TEST SHEET
  
  
 2) THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE
 LOCATION OF WHERE THE TILE
 WILL BE REPLACED.
  
 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION,
 MODIFICATION, OR REHABILITATION,
 CONSTRUCTION DOCUMENTS AND SHOP DRAWINGS SHALL BE
 SUBMITTED, REVIEWED, AND
 APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN
 SECTION 1.14.
  
 FOR THE OFFICIAL RECORD PLEASE PROVIDE A FLOOR PLAN
 INDICATING THE AREAS OF REPLACEMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED
 NARRATIVE RESPONSES TO THE ABOVE.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  