| 2022-04-26 13:35:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION ON THE APPLICATION OF |
| | "REPLACE TILE" |
| | |
| | TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT |
| | CERAMIC/PORCELAIN/MARBLE/CEMENT |
| | IT CAN BE VINYL/LAMINATE ETC AND IS MANUFACTURED FROM |
| | AROUND THE WORLD AND NOT ALL ARE |
| | TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD PLEASE PROVIDE THE TILE TYPE |
| | I.E. CERAMIC, MARBLE, TERRACOTTA, STONE |
| | WHICH WOULD NOT REQUIRE A SPEC SHEET. |
| | |
| | FOR OTHER TYPE OF TILE PRODUCT TYPE I.E. VINYL OR VINYL |
| | PLANKS, CORK, WOOD PLEASE PROVIDE |
| | THE MANUFACTURE PRODUCT FLAME SPREAD/PRODUCT SAFETY |
| | TEST SHEET |
| | |
| | |
| | 2) THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE |
| | LOCATION OF WHERE THE TILE |
| | WILL BE REPLACED. |
| | |
| | 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION, |
| | MODIFICATION, OR REHABILITATION, |
| | CONSTRUCTION DOCUMENTS AND SHOP DRAWINGS SHALL BE |
| | SUBMITTED, REVIEWED, AND |
| | APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN |
| | SECTION 1.14. |
| | |
| | FOR THE OFFICIAL RECORD PLEASE PROVIDE A FLOOR PLAN |
| | INDICATING THE AREAS OF REPLACEMENT. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED |
| | NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |