| Permit Number |
22040542 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-10-12 13:19:51 | 3RD GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2415.11 - THE PORTION OF GAS LINE TO THE | | | TANKLESS WATER HEATER IS STILL SHOWN AS GALVANIZED AND | | | IS NOT APPROVED FOR UNDERGROUND, EVEN WHEN ENCASED IN A | | | SLEEVE IT IS STILL NOT ALLOWED UNDERGROUND. IT WOULD | | | ONLY BE ALLOWED UNDERGROUND IF IF WAS PROTECTED PER | | | G2415.11.2. TYPICALLY IT WOULD TRANSITION TO CSST | | | OUTSIDE AND USE AN APPROVED UNDERGROUND TYPE OF CSST. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] |
|