Plan Review Notes
Plan Review Notes For Permit 22040542
Permit Number 22040542
Review Stop G
Sequence Number 3
Notes
Date Text
2022-10-12 13:19:513RD GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2415.11 - THE PORTION OF GAS LINE TO THE
 TANKLESS WATER HEATER IS STILL SHOWN AS GALVANIZED AND
 IS NOT APPROVED FOR UNDERGROUND, EVEN WHEN ENCASED IN A
 SLEEVE IT IS STILL NOT ALLOWED UNDERGROUND. IT WOULD
 ONLY BE ALLOWED UNDERGROUND IF IF WAS PROTECTED PER
 G2415.11.2. TYPICALLY IT WOULD TRANSITION TO CSST
 OUTSIDE AND USE AN APPROVED UNDERGROUND TYPE OF CSST.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved