2022-08-11 07:31:402ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. 2020 FRC P3108.1 - THE SHOWER IN THE MASTER BATH -
 TWO TRAPS ARE NOT ALLOWED ON THE HIGH SIDE OF THE VENT
 CONNECTION. PLEASE RECONFIGURE SO THAT ONLY ONE TRAP IS
 UPSTREAM OF THE VENT CONNECTION.
  
 3. DONE
  
 4. NOT ADDRESSED -- 2020 FRC P3108.1 - THE BAR SINK IS
 NOT ALLOWED TO WET VENT THE WATER CLOSET. ONLY BATHROOM
 GROUP FIXTURES ARE ALLOWED TO BE USED AS WET VENTING
 FIXTURES FOR OTHER BATHROOM GROUP FIXTURES. THE BAR
 SINK MUST DISCHARGE DOWNSTREAM OF THE WET VENTED
 SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  