| Plan Review Notes For Permit 22040542 |
| Permit Number |
22040542 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-08-15 16:13:57 | THE FOLLOWING COMMENTS ARE FROM THE 1ST REVIEW CYCLE | | | AND STILL NEED TO BE ADDRESSED: | | | | | | 1) THE DOCUMENTS IN THE SUPPORTING DOCUMENTS FOLDER | | | LABELED ENERGY CALCULATIONS ARE NOT ENERGY | | | CALCULATIONS, THEY ARE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. RELABEL THIS DOCUMENT AND PROVIDE THE | | | ENERGY CALCULATIONS. FEC 101.5.1.1.2 THE ENERGY | | | CALCULATIONS STILL HAVE NOT BEEN SUBMITTED. | | | | | | 2) IT APPEARS THAT AHU-4 IS SUPPLY AIR TO THE GARAGE | | | AND THE LIVING SPACE. THIS CANNOT HAPPEN SO PLEASE | | | CORRECT THE DESIGN. FRC M1601.6 | | | |
|