Plan Review Notes
Plan Review Notes For Permit 22040542
Permit Number 22040542
Review Stop G
Sequence Number 2
Notes
Date Text
2022-10-07 10:45:433RD GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
  
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 THE CHANGES MADE HAVE CREATED NEW COMMENTS.
  
 1. 2020 FRC G2415.11.1 - IT APPEARS THAT THE PORTION OF
 PIPING GOING TO TWH1 IS GALVANIZED. GALVANIZED PIPE IS
 NOT ALLOWED UNDER GROUND. PE IS NOT ALLOWED WITHIN THE
 BUILDING EITHER (G2415.17.1). PLEASE RECONFIGURE THE
 METHOD AND PIPING MATERIAL FOR TWH1.
  
 2. 2020 FRC G2415.14/G2415.14.1 - PIPING BENEATH
 BUILDINGS IS PROHIBITED UNLESS IT IS ENCASED IN CONDUIT
 IN ACCORDANCE WITH THIS SECTION. PLEASE DETAIL THE
 SLEEVE TO SHOW COMPLIANCE WITH G2415.14.1 SINCE ONE END
 TERMINATES OUTDOORS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  