| 2022-08-17 09:06:28 | ELECTRIC REVIEW FAILED |
| | 1) CONDUCTORS DETAILED, ON SHEET E 100, AS 2 SETS OF |
| | 1/0, WITH AN MAXIMUM AMPACITY OF 300 AMPS, BETWEEN ATS, |
| | AND LOAD CENTER, A, ARE INCORRECTLY SIZED, AS PER NEC |
| | 310.15 (B)(7)(2) AND NEC 110.14 (C)(1)(B)(1) AND (2). |
| | CONDUCTORS OVER 100 AMPERES SHALL BE LIMITED TO SIZING |
| | AT 75 DEGREE C TEMPERATURES AND SERVICE CONDUCTORS OR |
| | FEEDERS SERVING THE ENTIRE LOAD OF A SINGLE-FAMILY |
| | DWELLING SHALL BE SIZED AT 83% OF THE SERVICE RATING. |
| | THESE CONDUCTORS SHOULD BE SIZED FOR A MINIMUM AMPACITY |
| | OF 400 AMP X 83% = 332 AMPS. PLEASE CORRECT CONDUCTOR |
| | SIZE AS APPLICABLE. |
| | 2) CONDUCTORS DETAILED, ON SHEET E 100, AS 2/0, WITH A |
| | MAXIMUM AMPACITY OF 175 AMPS, BETWEEN LOAD CENTER, A, |
| | AND LOAD CENTER, MP, ARE INCORRECTLY SIZED, AS PER NEC |
| | 310.15 AND NEC 110.14 (C)(1)(B)(1) AND (2). CONDUCTORS |
| | OVER 100 AMPERES SHALL BE LIMITED TO SIZING AT 75 |
| | DEGREE C TEMPERATURES AND SERVICE CONDUCTORS OR |
| | FEEDERS, ONLY, SERVING THE ENTIRE LOAD OF A |
| | SINGLE-FAMILY DWELLING SHALL BE SIZED AT 83% OF THE |
| | SERVICE RATING. THESE CONDUCTORS DO NOT FEED THE ENTIRE |
| | LOAD OF THE DWELLING, AND, THEREFORE, MUST BE SIZED AT |
| | 100 %. THESE CONDUCTORS SHOULD BE SIZED FOR A MINIMUM |
| | AMPACITY OF 200 AMPERES. PLEASE CORRECT CONDUCTOR SIZE |
| | AS APPLICABLE. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |