Plan Review Notes
Plan Review Notes For Permit 22040542
Permit Number 22040542
Review Stop E
Sequence Number 2
Notes
Date Text
2022-08-17 09:06:28ELECTRIC REVIEW FAILED
 1) CONDUCTORS DETAILED, ON SHEET E 100, AS 2 SETS OF
 1/0, WITH AN MAXIMUM AMPACITY OF 300 AMPS, BETWEEN ATS,
 AND LOAD CENTER, A, ARE INCORRECTLY SIZED, AS PER NEC
 310.15 (B)(7)(2) AND NEC 110.14 (C)(1)(B)(1) AND (2).
 CONDUCTORS OVER 100 AMPERES SHALL BE LIMITED TO SIZING
 AT 75 DEGREE C TEMPERATURES AND SERVICE CONDUCTORS OR
 FEEDERS SERVING THE ENTIRE LOAD OF A SINGLE-FAMILY
 DWELLING SHALL BE SIZED AT 83% OF THE SERVICE RATING.
 THESE CONDUCTORS SHOULD BE SIZED FOR A MINIMUM AMPACITY
 OF 400 AMP X 83% = 332 AMPS. PLEASE CORRECT CONDUCTOR
 SIZE AS APPLICABLE.
 2) CONDUCTORS DETAILED, ON SHEET E 100, AS 2/0, WITH A
 MAXIMUM AMPACITY OF 175 AMPS, BETWEEN LOAD CENTER, A,
 AND LOAD CENTER, MP, ARE INCORRECTLY SIZED, AS PER NEC
 310.15 AND NEC 110.14 (C)(1)(B)(1) AND (2). CONDUCTORS
 OVER 100 AMPERES SHALL BE LIMITED TO SIZING AT 75
 DEGREE C TEMPERATURES AND SERVICE CONDUCTORS OR
 FEEDERS, ONLY, SERVING THE ENTIRE LOAD OF A
 SINGLE-FAMILY DWELLING SHALL BE SIZED AT 83% OF THE
 SERVICE RATING. THESE CONDUCTORS DO NOT FEED THE ENTIRE
 LOAD OF THE DWELLING, AND, THEREFORE, MUST BE SIZED AT
 100 %. THESE CONDUCTORS SHOULD BE SIZED FOR A MINIMUM
 AMPACITY OF 200 AMPERES. PLEASE CORRECT CONDUCTOR SIZE
 AS APPLICABLE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  