| Plan Review Notes For Permit 22040542 |
| Permit Number |
22040542 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-08-18 10:30:42 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA | | | PRODUCT APPROVALS FL18655, FL21061, FL21195, FL5259, | | | FL15279, FL6332 AND FL17908. FRONT PAGES ARE NEEDED TO | | | DETERMINE IF THE PRODUCT IS APPROVED BY THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. | | | | | | 2) PLEASE PROVIDE A NOTE ON THE DRAWINGS FOR THE | | | TERMITE PROTECTION - FBC R318 | | | | | | 3) THE ELEVATION CERTIFICATE NEEDS CORRECTIONS - C2(A) | | | ELEVATION SHOWN SHOULD BE THE LOWEST FLOOR ELEVATION | | | (LIVING ROOM IS LOWER THAN MAIN HOUSE) - FBC | | | 107.3.5.1.1 | | | | | | 4) DRAWING A-101.1 SHOWS THE GARAGE FLOOR AT 9.00 AT | | | THE DOOR TO THE LIVING SPACE - - PLEASE SHOW THE LOWEST | | | FLOOR ELEVATION AT THE OVERHEAD DOOR OPENING - - OR YOU | | | WILL NEED TO SHOW FLOOD VENTS PER FBC R322.2.2 - | | | | | | 5) UNABLE TO FIND THE INTERIOR DOOR SCHEDULE - R302.5.1 | | | OPENING PROTECTION. | | | OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM | | | USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED. | | | OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL | | | BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 13/8 | | | INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMBCORE | | | STEEL DOORS NOT LESS THAN 13/8 INCHES (35 MM) THICK, OR | | | 20-MINUTE FIRE-RATED DOORS. |
|