| 2022-04-28 15:42:35 | 1ST PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.2.1 - YOU'VE DETAILED A GAS |
| | WATER HEATER BUT I DO NOT SEE A GAS DIAGRAM. EITHER |
| | SUPPLY A GAS DIAGRAM AND A GAS SUB PERMIT FOR THIS |
| | MASTER PERMIT OR HAVE A SEPERATE GAS PERMIT IN PLACE TO |
| | SATISFY THIS COMMENT. |
| | |
| | 2. 2020 FRC P3108.1 - THE MASTER BATH SHOWER SHOWS A |
| | VENT ON P-100 AND NOT ON P-200. PLEASE MAKE THEM MATCH. |
| | ALSO, BOTH TRAPS ARE NOT ALLOWED ON THE HIGH SIDE OF |
| | THE VENT CONNECTION. PLEASE RECONFIGURE SO THAT ONLY |
| | ONE TRAP IS UPSTREAM OF THE VENT CONNECTION. |
| | |
| | 3. 2020 FRC P3108.1 - THE LAVATORIES IN THE BATHROOM |
| | NEAR THE CLOTHES WASHER HAS TWO TRAPS UPSTREAM OF THE |
| | VENT CONNECTION. ONLY ONE TRAP IS ALLOWED UPSTREAM OF |
| | THE VENT CONNECTION. |
| | |
| | 4. 2020 FRC P3108.1 - THE BAR SINK IS NOT ALLOWED TO |
| | WET VENT THE WATER CLOSET. ONLY BATHROOM GROUP FIXTURES |
| | ARE ALLOWED TO BE USED AS WET VENTING FIXTURES FOR |
| | OTHER BATHROOM GROUP FIXTURES. THE BAR SINK MUST |
| | DISCHARGE DOWNSTREAM OF THE WET VENTED SYSTEM. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |