| 2022-05-11 10:34:40 | 1ST REVIEW FMC |
| | PERMIT: 22040542 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. I SPOKE TO THE MECHANICAL |
| | ENGINEER, HE WAS DRIVING AND COULDN?T TALK AND SAID HE |
| | WOULD CALL BACK IN 10 MINUTES. I DID NOT HEAR BACK. MY |
| | COMMENTS ARE LISTED BELOW: |
| | |
| | 1) THE DOCUMENTS IN THE SUPPORTING DOCUMENTS FOLDER |
| | LABELED ENERGY CALCULATIONS ARE NOT ENERGY |
| | CALCULATIONS, THEY ARE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. RELABEL THIS DOCUMENT AND PROVIDE THE |
| | ENERGY CALCULATIONS. FEC 101.5.1.1.2 |
| | |
| | 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THE |
| | LOGGIA INDICATES A TOTAL CONDITIONED AREA OF 566 SQ. |
| | FT., SHEET A-003 INDICATES A TOTAL CONDITIONED SQ. FT. |
| | OF 628. PLEASE BE CONSISTENT. FBC 107.2.1 |
| | |
| | 3) THE MECHANICAL PLANS ARE NOT CLEAR AS TO THE |
| | LOCATION OF AHU-1 AND AHU-4. THEY BOTH ARE SHOWN ON THE |
| | FIRST AND SECOND FLOOR DRAWINGS. IS AHU-1 HUNG BELOW |
| | THE CEILING IN THE GARAGE? IS AHU-4 IN THE 2ND STORY |
| | ATTIC AREA THE SYSTEM BEING DUCTED TO THE GALLERY, |
| | BEDROOM AND THE FIRST FLOOR GARAGE? FBC 107.2.1 |
| | |
| | 4) AHU-1 THE RETURN IS BEING TAKEN FROM THE MASTER |
| | CLOSET. REMOVE FROM THE CLOSET AS IT CANNOT BE LOCATED |
| | IN A CLOSET. FRC M1602.2 |
| | |
| | 5) SHEET M-101: AHU-5: THERE IS A 4X12 SUPPLY GRILLE IN |
| | THE BATHROOM BUT NO DUCT SHOWN FOR THE SUPPLY. SHOW THE |
| | DUCTWORK FOR THIS GRILLE. FBC 107.2.1 |
| | |
| | 6) SHEET M-102: AHU-6: REMOVE THE RETURN AIR GRILLE |
| | FROM THE GUEST ROOM #2 WIC. FRC M1602.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |