| 2022-08-11 07:44:37 | 1ST GAS REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FRC G2415.11.2 - THE UNDERGROUND GAS PIPING |
| | CANNOT BE SCH 40 METALLIC PIPE. PLEASE DETAIL AN |
| | APPROVED GAS PIPING FOR ALL UNDERGROUND SECTIONS. |
| | |
| | 2. 2020 FRC G2415.17.1 - PLASTIC PIPE (P.E) IS NOT |
| | ALLOWED WITHIN OR UNDER ANY BUILDING. YOUR ROUTING |
| | APPEARS TO CONFLICT WITH THAT CODE. PLEASE CLARIFY THE |
| | ROUTING. |
| | |
| | 3. ACCORDING TO THE INDICATED INLET PRESSURE AND |
| | PRESSURE DROP, YOU WOULD BE USING TABLE 402.4(2). WITH |
| | A LONGEST RUN OF 260' AND A TOTAL LOAD OF 958,000 BTU, |
| | YOU APPEAR TO BE UNDERSIZED. ACCORDING TO THE LONGEST |
| | RUN METHOD, YOU WOULD NEED 2 1/2" ON THE 1ST PIECE OF |
| | PIPING. PLEASE CLARIFY THE GAS PRESSURE, AND RESUBMIT |
| | THE SIZING. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |