Plan Review Notes
Plan Review Notes For Permit 22040542
Permit Number 22040542
Review Stop G
Sequence Number 1
Notes
Date Text
2022-08-11 07:44:371ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2415.11.2 - THE UNDERGROUND GAS PIPING
 CANNOT BE SCH 40 METALLIC PIPE. PLEASE DETAIL AN
 APPROVED GAS PIPING FOR ALL UNDERGROUND SECTIONS.
  
 2. 2020 FRC G2415.17.1 - PLASTIC PIPE (P.E) IS NOT
 ALLOWED WITHIN OR UNDER ANY BUILDING. YOUR ROUTING
 APPEARS TO CONFLICT WITH THAT CODE. PLEASE CLARIFY THE
 ROUTING.
  
 3. ACCORDING TO THE INDICATED INLET PRESSURE AND
 PRESSURE DROP, YOU WOULD BE USING TABLE 402.4(2). WITH
 A LONGEST RUN OF 260' AND A TOTAL LOAD OF 958,000 BTU,
 YOU APPEAR TO BE UNDERSIZED. ACCORDING TO THE LONGEST
 RUN METHOD, YOU WOULD NEED 2 1/2" ON THE 1ST PIECE OF
 PIPING. PLEASE CLARIFY THE GAS PRESSURE, AND RESUBMIT
 THE SIZING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  