| 2022-05-24 09:43:29 | ELECTRIC REVIEW FAILED |
| | 1) IT APPEARS THE ELECTRICAL RISER DIAGRAM IS |
| | ATTEMPTING TO DETAIL A 300 AMP SERVICE. THE METER MAIN |
| | IS DETAILED AS 400-AMP. PLEASE DETAIL THE OVERCURRENT |
| | PROTECTION IN THIS METER MAIN AS 300-AMP OR DETAIL HOW |
| | THIS RISER COMPLIES WITH NEC 110.3, NEC 310.15 |
| | 2) PLEASE DETAIL CONDUCTOR SIZES BETWEEN METER MAIN AND |
| | ATS. NEC 215.5 |
| | 3) IT APPEARS LOAD CENTER B IS FED WITH INCORRECT SIZED |
| | CONDUCTORS. PLEASE DETAIL CORRECT SIZED CONDUCTORS OR |
| | DETAIL HOW THESE CONDUCTORS COMPLY WITH NEC 310.15 |
| | (B)(7)(2). PLEASE NOTE IN ORDER FOR FEEDER OR SERVICE |
| | CONDUCTORS TO BE REDUCED IN AMPACITY TO 83%, THEY MUST |
| | SERVE THE ENTIRE LOAD ASSOCIATED WITH THE STRUCTURE |
| | 4) PLEASE PROVIDE PANEL SCHEDULES FOR ALL LOAD CENTERS. |
| | NEC 215.5 AND FBC 107.2 |
| | 5) PLEASE DETAIL GROUNDING ELECTRODE SYSTEM FOR LOAD |
| | CENTER PH OR DETAIL HOW THIS PANEL COMPLIES WITH NEC |
| | 250.32 |
| | 6) PLEASE DETAIL NOTES STATING GENERATOR, POOL, AND LOW |
| | VOLTAGE WIRING REQUIRES A SEPARATE PERMIT |
| | 7) PLEASE DETAIL THE REQUIRED RECEPTACLE AT CONDENSING |
| | UNITS AS REQUIRED BY NEC 210.63 |
| | 8) PLEASE DETAIL ELEVATOR LOAD IN LOAD CALCULATIONS. |
| | NEC 215.5 |
| | 9) PLEASE PROVIDE ELEVATOR SPECIFICATIONS. FBC 107.2 |
| | 10) PLEASE DETAIL SMOKE/CARBON ALARMS AS REQUIRED |
| | R315.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |