2022-05-24 09:43:29ELECTRIC REVIEW FAILED
 1) IT APPEARS THE ELECTRICAL RISER DIAGRAM IS
 ATTEMPTING TO DETAIL A 300 AMP SERVICE. THE METER MAIN
 IS DETAILED AS 400-AMP. PLEASE DETAIL THE OVERCURRENT
 PROTECTION IN THIS METER MAIN AS 300-AMP OR DETAIL HOW
 THIS RISER COMPLIES WITH NEC 110.3, NEC 310.15
 2) PLEASE DETAIL CONDUCTOR SIZES BETWEEN METER MAIN AND
 ATS. NEC 215.5
 3) IT APPEARS LOAD CENTER B IS FED WITH INCORRECT SIZED
 CONDUCTORS. PLEASE DETAIL CORRECT SIZED CONDUCTORS OR
 DETAIL HOW THESE CONDUCTORS COMPLY WITH NEC 310.15
 (B)(7)(2). PLEASE NOTE IN ORDER FOR FEEDER OR SERVICE
 CONDUCTORS TO BE REDUCED IN AMPACITY TO 83%, THEY MUST
 SERVE THE ENTIRE LOAD ASSOCIATED WITH THE STRUCTURE
 4) PLEASE PROVIDE PANEL SCHEDULES FOR ALL LOAD CENTERS.
 NEC 215.5 AND FBC 107.2
 5) PLEASE DETAIL GROUNDING ELECTRODE SYSTEM FOR LOAD
 CENTER PH OR DETAIL HOW THIS PANEL COMPLIES WITH NEC
 250.32
 6) PLEASE DETAIL NOTES STATING GENERATOR, POOL, AND LOW
 VOLTAGE WIRING REQUIRES A SEPARATE PERMIT
 7) PLEASE DETAIL THE REQUIRED RECEPTACLE AT CONDENSING
 UNITS AS REQUIRED BY NEC 210.63
 8) PLEASE DETAIL ELEVATOR LOAD IN LOAD CALCULATIONS.
 NEC 215.5
 9) PLEASE PROVIDE ELEVATOR SPECIFICATIONS. FBC 107.2
 10) PLEASE DETAIL SMOKE/CARBON ALARMS AS REQUIRED
 R315.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved