Plan Review Notes
Plan Review Notes For Permit 22040542
Permit Number 22040542
Review Stop B
Sequence Number 1
Notes
Date Text
2022-07-07 10:42:43NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA
 PRODUCT APPROVALS LISTED ON THE DRAWINGS. FRONT PAGES
 ARE NEEDED TO DETERMINE IF THE PRODUCT IS APPROVED BY
 THE FLORIDA PRODUCT APPROVAL SYSTEM.
  
 2) PLEASE SHOW THE SITE STORM WATER DRAINAGE ON THE
 SITE PLAN OR PROVIDE A SEPARATE STORM WATER PLAN. FBC
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)
  
 3) PLEASE SHOW THE TYPE OF TERMITE PROTECTION - FBC
 R318
  
 4) DRAWING S-500 ROOF WIND LOADS - PLEASE SHOW THE WIND
 PRESSURES FOR ALL ROOF ZONES INVOLVED
 (1,2E,2N,2R,3,3E,3R ETC..) PER FBC TABLE R301.2(2)
  
 5) ON THE PROVIDED ROOF TILE UNDERLAYMENT PRODUCT
 APPROVAL - THERE ARE MANY DIFFERENT SYSTEMS TO BE USED
 - PLEASE CIRCLE THE ROOF SYSTEM TO BE USED ON THE
 PRODUCT APPROVAL MAKING SURE THAT THE WIND PRESSURE
 MEETS THE REQUIRED WIND PRESSURE PER THE DRAWINGS.
  
 6) THE NANA FOLDING DOOR PRODUCT APPROVAL PROVIDED HAS
 A HEIGHT LIMIT AT 8' - THE DRAWINGS SHOW THE DOOR TO BE
 10' HIGH - PLEASE CLARIFY.
  
 7) PLEASE SHOW THE EQUIPMENT PAD ELEVATIONS TO MEET THE
 FEMA AND CITY ORD. REQUIREMENTS (2' ABOVE BASE FLOOD
 ELEVATION) SEC. 18-296 (A) (5) AND FBC R322.1.6
  
 8) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE -
 FBC 107.3.5.1.1
  
 9) A SEPARATE PERMIT IS REQUIRED FOR - EXISTING
 BUILDING DEMO, POOL LOGGIA, SITEWALL, FENCING. PLEASE
 ACKNOWLEDGE THIS.
  
 10) STRUCTURAL DRAWINGS SHOW A SLOPE ON THE GARAGE SLAB
 AS IT SHOULD - PLEASE SHOW THE LOWEST FLOOR ELEVATION
 AT THE DOOR OPENING - - OR YOU WILL NEED TO SHOW FLOOD
 VENTS PER FBC R322.2.2 - ELEVATION OF THE MIN. 9.00
 NAVD IS SHOWN IN THE CENTER OF THE GARAGE - NEAR THE
 DOOR WILL BE LOWER THAN THE 2' ABOVE FEMA BASE FLOD
 ELEVATION - WHICH WILL REQUIRE FLOOD VENTS FOR THE
 GARAGE WALLS.