| 2022-04-26 16:02:46 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22040501 |
| | 4/26/22 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | RECIRCULATION EQUIPMENT- PUMP, FILTER, HEATER, AND MAIN |
| | TRAIN ASSEMBLY- SECS. R4501.6.6, R4501.7.2, R4501.14.1 |
| | FBC RES. |
| | |
| | 2) SHEET 3: PLEASE UPDATE ITEM #1 OF THE SPECIFICATIONS |
| | IN COMPLIANCE WITH SEC. R4501.6.1 CONFORMANCE STANDARDS |
| | FBC RES. |
| | |
| | 3) PLEASE NOTE THAT A BACKFLOW PREVNTER SHALL BE |
| | INSTALLED ON THENWATER SERVICE IN ACCORDANCE WITH THE |
| | CITY OF WEST PALM BEACH UTYILITIES CROSS-CONNECTION |
| | MANUAL- A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN |
| | A SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION OF THE POOL BY THE BUILDING |
| | DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL |
| | OPERATIONS DEPT.AT 561-822-2210 FOR FURTHER |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |