| 2022-12-27 07:52:13 | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22040495 |
| | ADD: 2480 PRESIDENTIAL WAY # 303 |
| | CONT: J & C CONSTRUCTION |
| | TEL: 954-880-4368 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | DATE: TUES. DEC. 27TH/2022 |
| | ACTION: DENIED |
| | PLEASE, PLEASE CALL ME SO WE CAN DISCUSS THE PERMIT |
| | ISSUES!!!!!!!!!!!!!! |
| | |
| | 1-2) COMPLIED. |
| | |
| | 3) 4TH REQUEST. NARRATIVE STATES IF YOU NEED ANYTHING |
| | PLEASE GIVE US A CALL. NO CONTRACTOR SIGNED ON, THE |
| | NARRATIVE DOES NOT PROVIDE A TEL. CONTACT NUMBER. |
| | PROJECT DOCS PROVIDES ONLY A CONTACT E-MAIL OF: |
| | [email protected]. IN THIS REVIEW THE NARRATIVE |
| | STATES (1) UNDERLAYMENT USED TEST REPORT ON THE FILE |
| | NAME: ECLIPSE II-FLYER GREEN GUARD PDF. NOA WHISPER-MAT |
| | CS PDF. |
| | |
| | SUBMITTED 12/21/22 ECLIPSE-II-FLYER-GREEN-GUARD, THIS |
| | IS A SALES BROCHURE NOT A TEST REPORT, THE LISTED 3 |
| | TEST REPORTS ARE LISTED BELOW IN SECTIONS 3A, 3B & 3C. |
| | ECLIPSE II-FLYER GREEN GUARD IS AN UNDERLAYMENT TO BE |
| | USED WITH FLOATING LAMINATES, ENGINEERED WOOD AND OR |
| | SOLID RIGID CORE VINYL. 2 PAGES. THE CITY OF WPB DOES |
| | NOT HAVE ANY TEST REPORTS (3) FOR THIS PRODUCT. FLOOR |
| | PLAN THIS ROUND SHOWS THIS PRODUCT TO BE INSTALLED IN |
| | THE DINING ROOM & LIVING ROOM. SUGGEST A NEW PRODUCT, |
| | IF THIS PRODUCT IS ALREADY INSTALLED PLEASE INDICATE AS |
| | SUCH AND WHAT TYPE OF FINISH FLOORING WAS REMOVED. |
| | |
| | SUBMITTED 12/21/22 THE SAME SUBMITTAL DAY. WHISPER MAT |
| | CS WHICH IS TO BE USED WITH EITHER MARBLE AND OR TILE, |
| | AGAIN SALES BROCHURE. THE BUILDING FLOOR PLAN NOW |
| | DESIGNATES (2) TYPES OF FLOOR FINISHES IN THE ENTRY & |
| | KITCHEN TILE AND THE UNDERLAYMENT WHISPER-MAT CS WHICH |
| | WE DO HAVE HE 3 REQUIRED TEST REPORTS WHICH WE HAVE |
| | UPLOADED. |
| | |
| | 3RD REQUEST. SUBMITTED SALES BROCHURE PRIVACY ULTIMATE |
| | TILE / STONE UNDERLAYMENT, THIS IS NOT THE 3 REQUIRED |
| | TEST REPORTS. THE BUILDING FLOOR PLAN DATED 11/29/2022 |
| | STATES INSTALL SOUNDPROOFING ECLIPSE II SOUNDPROOFING. |
| | IT IS ASSUMED FOR TILE OR MARBLE FLOORING, THIS REVIEW |
| | NONE OF THE 3 TEST REPORTS WERE SUBMITTED. |
| | |
| | 2ND REQUEST. THE DEMO FLOOR PLAN INDICATES THE REMOVAL |
| | OF FLOOR TILE NOTE 2 BUT DOES NOT INDICATE THE NEW |
| | FLOOR FINISH MATERIAL NOR SOUND UNDERLAYMENT. FLOOR |
| | INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, |
| | MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD |
| | FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT |
| | TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND |
| | MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE |
| | STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO |
| | DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 3A) 4TH REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 3B) 4TH REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 3C) 4TH REQUEST. FLAME SPREAD- FBC-B 2020 603.1. |
| | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |