Plan Review Notes
Plan Review Notes For Permit 22040495
Permit Number 22040495
Review Stop B
Sequence Number 4
Notes
Date Text
2022-12-27 07:52:132020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22040495
 ADD: 2480 PRESIDENTIAL WAY # 303
 CONT: J & C CONSTRUCTION
 TEL: 954-880-4368
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUES. DEC. 27TH/2022
 ACTION: DENIED
 PLEASE, PLEASE CALL ME SO WE CAN DISCUSS THE PERMIT
 ISSUES!!!!!!!!!!!!!!
  
 1-2) COMPLIED.
  
 3) 4TH REQUEST. NARRATIVE STATES IF YOU NEED ANYTHING
 PLEASE GIVE US A CALL. NO CONTRACTOR SIGNED ON, THE
 NARRATIVE DOES NOT PROVIDE A TEL. CONTACT NUMBER.
 PROJECT DOCS PROVIDES ONLY A CONTACT E-MAIL OF:
 [email protected]. IN THIS REVIEW THE NARRATIVE
 STATES (1) UNDERLAYMENT USED TEST REPORT ON THE FILE
 NAME: ECLIPSE II-FLYER GREEN GUARD PDF. NOA WHISPER-MAT
 CS PDF.
  
 SUBMITTED 12/21/22 ECLIPSE-II-FLYER-GREEN-GUARD, THIS
 IS A SALES BROCHURE NOT A TEST REPORT, THE LISTED 3
 TEST REPORTS ARE LISTED BELOW IN SECTIONS 3A, 3B & 3C.
 ECLIPSE II-FLYER GREEN GUARD IS AN UNDERLAYMENT TO BE
 USED WITH FLOATING LAMINATES, ENGINEERED WOOD AND OR
 SOLID RIGID CORE VINYL. 2 PAGES. THE CITY OF WPB DOES
 NOT HAVE ANY TEST REPORTS (3) FOR THIS PRODUCT. FLOOR
 PLAN THIS ROUND SHOWS THIS PRODUCT TO BE INSTALLED IN
 THE DINING ROOM & LIVING ROOM. SUGGEST A NEW PRODUCT,
 IF THIS PRODUCT IS ALREADY INSTALLED PLEASE INDICATE AS
 SUCH AND WHAT TYPE OF FINISH FLOORING WAS REMOVED.
  
 SUBMITTED 12/21/22 THE SAME SUBMITTAL DAY. WHISPER MAT
 CS WHICH IS TO BE USED WITH EITHER MARBLE AND OR TILE,
 AGAIN SALES BROCHURE. THE BUILDING FLOOR PLAN NOW
 DESIGNATES (2) TYPES OF FLOOR FINISHES IN THE ENTRY &
 KITCHEN TILE AND THE UNDERLAYMENT WHISPER-MAT CS WHICH
 WE DO HAVE HE 3 REQUIRED TEST REPORTS WHICH WE HAVE
 UPLOADED.
  
 3RD REQUEST. SUBMITTED SALES BROCHURE PRIVACY ULTIMATE
 TILE / STONE UNDERLAYMENT, THIS IS NOT THE 3 REQUIRED
 TEST REPORTS. THE BUILDING FLOOR PLAN DATED 11/29/2022
 STATES INSTALL SOUNDPROOFING ECLIPSE II SOUNDPROOFING.
 IT IS ASSUMED FOR TILE OR MARBLE FLOORING, THIS REVIEW
 NONE OF THE 3 TEST REPORTS WERE SUBMITTED.
  
 2ND REQUEST. THE DEMO FLOOR PLAN INDICATES THE REMOVAL
 OF FLOOR TILE NOTE 2 BUT DOES NOT INDICATE THE NEW
 FLOOR FINISH MATERIAL NOR SOUND UNDERLAYMENT. FLOOR
 INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) 4TH REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) 4TH REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) 4TH REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  