| Plan Review Notes For Permit 22040495 |
| Permit Number |
22040495 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-15 11:08:13 | FIRE COMMENTS: | | | PROVIDE DOCUMENTATION ON THE TYPE OF NEW TILE FLOORING | | | TO BE INSTALLED, SPECIFICALLY IF IT IS A COMBUSTIBLE | | | MATERIAL SUCH AS VINYL PLANK, SUPPLY THE INFORMATION ON | | | THE FIRE PERFORMANCE OF THE MATERIAL INCLUDING THE | | | CRITICAL RADIANT FLUX. NFPA 101 10.2.7 | | | WITH THE REMOVAL OF WALLS, AN EVALUATION SHALL BE | | | PERFORMED TO ENSURE ALL LIFE SAFETY SYSTEMS (FIRE | | | SPRINKLER AND/OR FIRE ALARM) PROVIDE ADEQUATE COVERAGE. | | | ANY AND ALL WORK ON ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED UNDER | | | SEPARATE PERMITS AND SHOP DRAWINGS BY QUALIFIED | | | CONTRACTORS. | | | ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR | | | FIRE ALARM) SHALL BE MAINTAINED OPERATIONAL DURING | | | DEMOLITION AND CONSTRUCTION AND ANY IMPAIRMENT TO THESE | | | SYSTEMS THAT EXCEEDS 4 CONTINUOUS HOURS IN DURATION | | | WILL REQUIRE THE IMPLEMENTATION OF A FIRE WATCH. | | | FIRE REVIEWER: | | | C. WALKER | | | 561-804-4762 | | | [email protected] | | | |
|