| Plan Review Notes For Permit 22040494 |
| Permit Number |
22040494 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-02 09:32:36 | 1ST REVIEW FMC | | | PERMIT: 22040494 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FEC | | | 101.5.1.1.2 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC R403.7.1 | | | | | | 3) PLEASE SHOW THE BATH EXHAUST FANS AND THE EXHAUST | | | TERMINATION LOCATION FOR EACH. FRC M1507.4 | | | | | | 4) PLEASE SHOW THE DRYER DUCT SIZE, MATERIAL AND | | | TERMINATION LOCATION. FRC M1502.3 | | | | | | 5) PLEASE PROVIDE A DETAIL DRAWING OF THE OUTDOOR | | | APPLIANCE ANCHORING. FRC M1307.2 | | | | | | 6) PLEASE SHOW THE CONDENSATE PIPE SIZE, MATERIAL AND | | | TERMINATION LOCATION. FRC M1411.3 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|